background image

1

6E 6128.c

6E 6128.c

res

7

6

on

off

5

4

3

2

1

ON

ON

OFF

OFF

enter

A
B

auto
manu

EG270

§

2 channels time switch -
weekly cycle

User instruction

´

Working principle :

The EG270 is a time switch for the automatic
control of electrical loads.
It is fully programmable with a maximum of 20
program steps to be divided between the two
channels. Each program step can be applied
to one or several days, maximising the use of
each memory location.
The front cover is sealable preventing 
unauthorised access after completion of 
programming.

Warning :

at the beginning of use, please

reset the device in order to clear the memory
before programming. 
This is achieved by using a pen to push the
reset button.

Presentation :

Display :

Œ

time



circuit status of channel A (ON or OFF)

Ž

circuit status of channel B (ON or OFF)



day of the week
(1 = Monday, 2 = Tuesday ....)

Buttons :



Mode selector : to select one of the  
following modes :

time setting

A

programming channel A

B

programming channel B

auto

running mode

manu

manual override

‘

1

” to “

7

” : selection of the days

’

on/off

” : chooses whether the circuit 

is on or off

“

+

” and “

-

” : changes settings

”

enter

” : to confirm

•

reset

” 

Time and day setting : 

1. Move mode selector to 
2. Select with key “

1

” to “

7

” , the actual day 

(1=Monday, 2 = Tuesday .)

3. Input time with buttons “

+

” and “

-

”.

Important :

The clock starts when exiting the time setting mode.

Programming channel A :

1. Move mode selector to “

A

”. 

2. Select with keys “

1

” to “

7

” the day(s) assigned  

to this program step. An arrow appears  
above each day concerned.

3. Input switching time with buttons “

+

” and “

-

”.

4. Input the type of switching with button “

on/off

” 

(for the first action ON is automatically proposed).

5. Enter this program step with button “

enter

”.

Program additional time settings by repeating  
steps 2 to 5.

Important :

To activate the program, move mode selector to

auto

”.

Programming channel B :

Move mode selector to “

B

”. 

Same way of programming as channel A.

Important :

To active the program, move mode selector to “

auto

”.

Running Auto mode 

This mode is the current displaying mode. 
It does not allow any modification.
Move mode selector to “

auto

”.

Display of the time, the day and the state of the two
channels.

To override the output :

Important :

the override must be identical on 

the two channels (channels A and B “ON”

“ON” or channels A and B “OFF”“OFF”).

Permanent override :

1. Move mode selector to “

manu

”.

2. Select the state of the outputs with key

on/off

”.

To switch back to automatic mode, move
mode selector to “

auto

”.

1

2

3

4

5

6

7

1

2

4

3

5

6

7

8

9

10

enter

reset

on

off

A
B

auto

manu

ON ON

1

2

3

4

5

6

7

enter

reset

on

off

A
B

auto

manu

To modify or delete a program step

on channel A or B :

1. Move mode selector to “

A

” or “

B

”.

2. Press “

enter

” repeatedly and select the 

program step to modify or to delete.

3. Modify :

- switching time with keys “

+

” or “

-

- days assigned with keys “

1

” to “

7

”.

(an arrow flashes above all days assigned, 
press once to add a day, press twice to 
cancel).

- state of the channel with key “

on/off

”. 

To delete a program step, press keys “

1

” to 

7

” in order to cancel all days assigned.

4. Confirm with the “

enter

” key.

3 4 5 6

2

1

L
N

EG270

9

8

7

10 11 12

A

B

Technical specifications :

Electrical characteristics :
- supply voltage : 230V AC +10/-15%   50/60Hz
- outputs : 2 changeover contact

μ 16A - 250V AC1.
μ 3A - 250V cos 

ϕ

= 0,6

1000 W incandescent lighting

- power consumption : 1 VA
- protection degree : IP20
- insulation class : II

Functional characteristics :
- accuracy : ± 1sec. / day at 20 °C
- operating reserve : lithium battery, 

total of three years.

Environment :
Operating temperature : -10 to +50 °C
Storage temperature :

-10 to +50 °C

Connection tunnel terminals : 
flexible : 0,5 to 2.5 mm

2

rigid : 0,5 to 4 mm

2

Dimensions : 3 modules (3x17,5mm)

Electrical connections :

1. Move mode selector to “

manu

”.

2. Select the state of the outputs with key

on/off

”.

3. Input with key “

+

” and “

-

” the override dura

tion : from 1 to 23 hours by steps of 1 hour.
Then from 1 to 27 days by steps of 1 day. 

4. Move mode selector to “

auto

”.

The state indication is flashing. This means a
timed override. Return to the initial program
after the duration.

To reset the time switch :

Press “

reset

“ to clear the program.

1. Move mode selector to “

manu

”.

2. Press key “

-

” or “

+

” until display -h. 

3. Move mode selector to “

auto

” to switch 

back to automatic mode.

Timed override :

To cancel the timed override : 

A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material of manufac-
turing defect. If any product is found to be defective it must be
returned via the installer and supplier (wholesaler). The warranty
is withdrawn if :
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
IEE wiring regulations and accepted practice within the industry at
the time of installation.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning goods.

Warranty

GB

1

2

3

4

5

6

7

enter

reset

on

off

A
B

auto

manu

ON ON

1

2

3

4

5

6

7

enter

reset

on

off

A
B

auto

manu

ON ON

1

2

3

4

5

6

7

enter

reset

on

off

ON ON

A
B

auto

manu

1

2

3

4

5

6

7

enter

reset

on

off

A
B

auto

manu

ON

ON ON

ON

1

2

3

4

5

6

7

enter

reset

on

off

A
B

auto

manu

ON

ON ON

ON

To check your program on channel A 
or B :

1. Move mode selector to “

A

” or “

B

”.

2. Press the “

enter

” key repeatedly to display

the different program steps (switching time,
days of the week and state of the channel 
ON or OFF).

 

http://waterheatertimer.org/Hagar-timers-and-manuals.html

_________________________________________________________________________

Reviews: