Programming :

1. To start programming, press key

Prog

”, the first program step

flashes.

2. Set the first switching time with key “

+

or “

-

3. Use the “

on/off

” button to choose between

circuit:

ON and circuit OFF.

ON = work authorization period.

OFF = work banning period.

4. Enter the settings by pressing

Prog

” (short press).

You must now choose

the days of the week

that the settings apply to.

5. With key “

+

” and “

-

”, display one after the

other each day of the week and select with

key “

on/off

” if the program applies to this

day or not.

Days to which the switching is to be applied

must be visible at the bottom of the display

e.g. 1 2 3 4 5 visible, means switching will

be applied Monday to Friday.

6. Press “

Prog

” to enter this program step.

7. To adjust the time settings

as well as the assignments to the

days of the week ;

Repeat operation 2 to 6 for further

programmes. (maximum 20)

If no buttons are pressed within 2 min.,

the device switches back to automatic mode

without recording your settings.

8. To record your settings and

return to automatic mode press

Prog

” for more than 2 seconds.

The programmable light sensitive switch EE171 has
two main functions:
• a light sensitive switch comprising:

Œ

Override selector switch to allow permanent
setting ON or OFF, auto or test mode.



Lighting range selector.

Ž

Potentiometer to set light level.



Indicator to show output switching.

• a programmer to establish the automatic

operating cycle.

The programmer comprises 4 keys:



on/off

to choose whether the circuit is on or off

‘

Prog

to set the program and scroll program

steps

’

reset

“

+

and

-

to change settings

On the display are indicated :
A. the current time
B.the working status ON (authorization) or

OFF (banning)

C.The days to which the program applies.

(1= Monday, 2 = Tuesday ...............7 = Sunday)

Setting time and day:

Press key + or -.
A continuous pressing on this keys will scroll up or
down minutes, hours and then days.

6L

E

00

28

31

A

EE171

Operating principle:

The EE171 programmable light sensitive
switch controls light sytems according to

a

program set by the user, depending on natu-
ral illumination.
- during the work authorization period, de-

pending on wether the measured light level
is below or above the required level, it will
be switched on or off.

- during the work banning period, the contact

remains open, whatever the light level is.

The light sensitive switch includes a built in
time delay which avoid unnecessary switching
due to temporary factors such as car beams
etc...

Description:

Lux

T

6:00

8:00

17:00

23:00

ON

ON

OFF

OFF

OFF

11

10

12

N

5

1

2

L

6

6E

05

85

a

230 V

50 Hz

16A 250V

10

11

12

AC1

test

auto

2000

50

Lux

100

5

12

12

77

88

99

10

10 11

11

66

11

22

33

44

55

12

7

8

9

10 11

6

1

2

3

4

5

on/off Prog

+

Œ




‘

’

“



Ž

To check your settings :

In automatic mode :

Press “

Prog

” repeatedly to display the day, the

time and the circuit status (ON or OFF).

To switch back to automatic mode, press

Prog

” for more than 2 sec.

To reset the time switch :

Press the “

reset

” button, the program will be

cancelled.

z

Programmable light

sensitive switch

y

Technical specification:

Electrical specification

- Voltage rating :

230V ~+10/-15% 50 Hz

240V~ +/-6%

- Consumption :

1,5 VA max.

- Output : 1 voltage free changeover contact
- Max. breaking capacity :
- AC1

16A 230V~

- Incandescent lamp

2000W 230V~

- Halogen lamp

1000W 230V~

- Fluorescent lamp :
- Uncompensated

1000W 230~

- Compensated in series (10µF)

1000W 230V~

- // compensated (15µF)

200W 230V~

- Duo

1000W 230V~

- Upstream protection:

circuit breaker 16 A

- Action type:

1B

- Pollution category:

2

- Rated impulse voltage:

4 kV

- Max. altitude:

<2000m

- Software structure:

class A

- Voltage and current declared for the needs

of EMC emissions tests:

230V~ / 0.5A

Functional characteristics

- 2 sensitivity ranges

5 to 100 lux

50 to 2000 lux

- Weekly cycle
- 8 predefined programs
- Program setting :

1 minute increments

- Accuracy :

± 6 min./ annum

- Operating reserve : lithium battery total of

3 years of supply failure

- On and off delay :

15 to 60 s.

- Working temperature :

-30 °C to +60 °C (cell),

-10 °C to +45 °C (Modular device)

- Storage temperature :

- 20 °C to +60 °C

- Protection class (cell) :

IP54

- Insulation class (cell) :

II

- Independent panel-mounted (DIN rail)

control device

Connection capacity

- Modular device :

0,5 to 4 mm

2

- Cell :

0,75 to 2,5 mm

2

- Max lenght between cell and modular

device :

50 m

- Mounting of the cell with 2 screws

Ø 2,5 mm

Size

- Between:

3

0

(17,5 mm x 3)

- Cell :

( 32 x 48 x 37 mm)

Permanent overrides

the override selector

Œ

allows permanent

overrides which have priority on programming

and the measured light level.

permanent override "ON"

permanent override "OFF"

Setting of the working level:

The test position of the override selector

Œ

makes easier the setting of the working level, it

removes the ON and OFF delay.
Select the sensitivity range which suits whith

the appliccation (selector



)

5 to 100 lux (low light level)

applica-

tion examples : public

lighting, shop

windows, signals..

50 to 2000 lux (high light level) applica-
tion examples : control of shades.

At the appropriate moment of the day, put the

selector

Œ

in “

test

” position ; turn the poten-

tiometer

Ž

up to the switching point (the indi-

cator



lights) ; put the selector back to

position “

auto

”, the normal operating mode of

the device.

Mounting of the cell:

To ensure a good working of the light sensitive

switch, the cell must not be influenced by arti-

ficial light or direct solar radiation and has to be

sheltered from dust and humidity.
In case of disconnection of the link between

the cell and the light sensitive switch, the out-

put of the device will be switched on.

test

auto

test

auto

L

N

1

10 11 12

2

5 6

A

Make sure the light sensitive switch is

unplugged before connecting the cell.

A warranty period of 24 months is offered on hager

products, from date of manufacture, relating to any material

of manufacturing defect. If any product is found to be de-

fective it must be returned via the installer and supplier (who-

lesaler). The warranty is withdrawn if:

- after inspection by hager quality control dept the device is

found to have been installed in a manner which is contrary

to IEE wiring regulations and accepted practice within the

industry at the time of installation.

- The procedure for the return of goods has not been

followed. Explanation of defect must be included when re-

turning goods.

z

Warranty

NOT APPLICABLE FOR AUSTRALIA

Correct Disposal of This product (Waste Electrical & Electronic
Equipment).

(Applicable in the European Union and other European countries
with separate collection systems).

This marking shown on the product or its literature indicates that it

hould not be disposed with other household wasted at the end of its working
life. To prevent possible harm to the environment or human health from un-
controlled waste disposal, please separate this from other types of wastes
and recycle it responsibly to promote the sustainable reuse of material re-
sources.
Household users should contact either the retailer where they purchased this
product, or their local government office, for details of where and how they
can take this item for environmentally safe recycling.
Business users should contact their supplier and check the terms and condi-
tions of the purchase contract. This product should not be mixed with other
commercial wastes of disposal.

Usable in all Europe

å

and in Switzerland

Load output connection: If load intensity

is >10A use cables with at least a 2.5mm²

diameter

This device must be installed only by

a qualified electrician according to the

installation standards in force in the

country.

Reviews: