6LE001872Ab
CDAxxxRA, CFAxxxRA
s
Jordfelsbrytare med automatisk
återställning och självtestfunktion
z
Automatic testing and reclosing
RCCB device
L
N
AUX
OFF
230 V
v
LOAD
L
N
2 Nm
2 Nm
0,4 Nm
3
≤ 2,5 mm
2
OK
OK
OK
OK
L N
L N
230 V
v
L L L N
L L L N
400 V
v
L L
L L
400 V
v
f+
ARD
N
N
L3
L2
L1
N
Last / Load
Nej / No
f+
ARD
N
L3
L2
L1
N
Last / Load
N
T
f+
ARD
N
L
Last / Load
N
T
f+
ARD
N
L
N
L
Last / Load
Nej / No
2P
4P
90
10
6
9
17,8
7,4
10
6
17,8
9
124,8
2P
4P
Teknisk data /
Technical characteristics
Distribution system
TT - TN
Rated operational voltage Ue
230 - 400 Vac
In
25 - 40 - 63 A
I
m
n
30 - 300 mA
Type
A [IR]
10000 A (gL 63 A In = 25 - 40 A, gL 80 A In = 63 A)
Off-load absorbed power
4 (cos = 0,2)
Reclosing absorbed power
41 (cos = 0,5)
Dissipated power at In
2P 2,2 W (25 A), 4P 3,5 W (25 A), 6 W
(40 A), 12 W (63 A)
Insulation voltage to earth
2500 Vac for 1 min.
Rated impulse withstand
voltage Uimp
4 kV
Blocking threshold Rdo
2/4P 8 kΩ IΔn 30 mA, 2,5 kΩ IΔn 300 mA
Reset threshold Rd
2/4P 16 kΩ IΔn 30 mA, 5 kΩ IΔn 300 mA
Time of reclosing
< 10 s
Time of automatic testing
< 7 s
Width
5 - 7 Modules
Operating temperature
-25°C
➡
+60°C, daily average ≤ 35°C
Auxiliary contact
Imax
Imin
5 ÷ 230 Vac / dc
100 mA (cos
= 1),
0,6 mA / AC12
Mått / Dimensions
Installation
Anslutning / Connexion
This device is to be installed only by a
professional electrician fitter according to
local applicable installation standards.
Apparaten får endast installeras av
behörig elektriker enligt i landet gällande
installationsnormer.
Ingripande är endast tillåten närenhet är
isolerad och enheten har varit avstängd
(kåpa förflyttas åt höger och hävarm
åtkomlig) /
Intervention is only permitted when the
unit is isolated and the device has been
switched off (slide moved to the right and
lever accessible)
≤ 35mm
2
6LE001872Ab
1