INSTALLATION
RACKMOUNTING
VENTILATION/
PLACEMENT
LINE VOLTAGE
The 9130 Amplifier is supplied in either a 17” Black Version, or a 19” Silver Version. The 19” model
has rackmounting holes provided for installation in equipment racks. The holes are on standard EIA
spacings.
Due to conflict with adjacent equipment, it may be advisable to remove the four rubber feet
from the bottom of the unit. The feet may be removed from the outside, with no dis-assembly of the
chassis necessary.
The 9130 Amplifier can produce considerable heat during normal operation. The amplifier should be
placed on a hard, smooth surface to allow air to circulate beneath the unit. Additionally, allow at least
one inch of free space on either side, and several inches above and behind the amplifier to allow air
circulation around the heatsinks. This is particularly important when the unit is installed in a closed
cabinet.
In applications where the amplifier is driving low impedance and/or low efficiency loudspeakers at high
levels, thermal shutdown may occur if inadequate ventilation is provided. If this occurs, it may be
necessary to move the amplifier to a location with better free air circulation.
The amplifier should be located at least several inches away from sensitive components, (such as
preamplifiers, tuners, CD players, turntables, etc.) due to the possibility of audible hum or buzz from
magnetic radiation.
The 9130 Amplifier is configurable for either 100, 120, or 230 volt operation. This is accomplished by
moving the Voltage Selector on the printed circuit board. The procedure is detailed in the section
“CHANGING LINE VOLTAGE RATING”.
Make sure that the unit is configured for your local AC line voltage before attempted use. The
configuration is labelled directly above the power cord connector. (Units wired for 230VAC may be used
over a range of 220 to 240VAC.)
OPERATION/CONNECTIONS
POWER CORD
CONNECTION/
POWER SWITCH
INPUTS
Units wired for 100 and 230 VAC are supplied without power cords. Local agents will supply cords with
male connectors appropriate to the local standard.
Units wired
for 120
VAC
are supplied with a detachable AC power cord. The female connector plugs
into the receptacle provided on the rear panel. This power cord is a standard IEC Type 320, 3-wire,
16 gauge assembly. Should replacement ever be necessary, be sure to replace it with an identical cord.
Never remove the grounding pin from the male end of the cord. In applications where a grounded outlet
is not available, a ground adaptor should be employed, with the ground tab or wire of the adaptor
connected to a suitable earth ground.
The AC power cord of the amplifier must be connected to a receptacle capable of delivering a minimum
of 600 watts. The convenience outlets of some preamplifiers are not rated for this power level. Before
connecting the amplifier, be sure to check the rating of such outlets, and take into account the power
consumption of any other connected components to determine the total maximum power consumption.
If the amplifier is connected to a component with a switched convenience outlet, then the amplifier’s
Power Switch may be left ON at all times, and the power controlled by the switched outlet. If the amplifier
is connected to an unswitched outlet, then the amplifier’s power should be controlled by the front panel
Power Switch.
All input connections to the amplifier must be performed with the amplifier off!
The left and right audio inputs to the amplifier are via standard RCA jacks. Connect these jacks to the
output of the preamplifier or other signal source.
When operating the amplifier in the Mono Mode, only the left channel input should be used.
-5-
Summary of Contents for 9130 series
Page 8: ... 7 ...
Page 16: ...a L c4w m IL bO I L ...