background image

69

Replacement Parts and Accessories

8.5 Mounting Plate Hardware for Directly Mounting to Pipe Wall

Sensor Type 

Part Number 

Submerged Pressure

4939

In-Pipe

3875

Summary of Contents for 911

Page 1: ...Catalog Number 4979 911 940 Intrinsically Safe Flow Meters USER MANUAL January 2010 Edition 11 HACH LANGE Company 2007 2010 All rights reserved Printed in the U S A...

Page 2: ......

Page 3: ...e Sampler Interface on Model 940 36 4 6 Sampler Receptacle 940 Only 37 4 6 1 Connecting the Sampler Cable to a 940 Flow Meter 38 4 6 2 Connecting a Non Sigma Sampler to a 940 Flow Meter 38 Section 5 S...

Page 4: ...locity Sensor Oil filled and Non oil 60 7 8 3 Replenishing the Oil 62 7 8 4 Changing the Submerged Area Velocity Sensor Desiccant 63 7 8 5 Replacing the Desiccant 64 Section 8 Replacement Parts and Ac...

Page 5: ...m cfh cfd m3s m3m m3h m3d Totalized Flow gal ft3 acre ft L m3 Data Storage Capacity 400 days of 1 level reading and 1 velocity reading at a 15 minute recording interval Data Types Level and Velocity S...

Page 6: ...Battery Life 330 days typical with a 15 minute recording interval 1 level and 1 velocity data download once per week 10 C 50 F also affected by site conditions User Interface Optically Isolated Interf...

Page 7: ...ion 1 2 W 12 VDC Cable Material Urethane sensor cable with air vent Cable Lengths Available Standard 9 15 23 and 30 5 m 30 50 75 and 100 ft Custom 30 75 76 m 101 250 ft maximum Cable Diameter 0 91 cm...

Page 8: ...e per degree of change Resolution 0 019 cm 0 0075 in Material ABS housing with ABS acoustical window Cable Length 7 62 to 30 48 m 25 to 100 ft Dimensions 15 24 cm x 5 7 cm 6 in x 2 25 in 1 When the se...

Page 9: ...trical equipment marked with this symbol may not be disposed off in European public disposal systems after 12 August of 2005 In conformity with European local and national regulations EU Directive 200...

Page 10: ...s are designed to be incapable of producing a spark or thermal effect that could ignite a mixture of flammable or combustible gases when properly installed in a Class 1 Division 1 Group C or Group D H...

Page 11: ...mm 2 in must be maintained between any non intrinsically safe conductors and intrinsically safe wiring or terminations The only exceptions allowed for minimum clearances are All intrinsically safe cir...

Page 12: ...1 and 940 Flow Meters on the dangers and risks associated with entry into confined spaces DANGER Additional training in Pre Entry Testing Ventilation Entry Procedures Evacuation Rescue Procedures and...

Page 13: ...edures must always be followed prior to entry into confined spaces and or locations where hazardous gases vapors mist dust or fibers may be present Note Before entering any confined space check with t...

Page 14: ...12 General Information...

Page 15: ...3 Choosing the Appropriate Meter and Sensor Combination Use Table 4 to determine which sensor to use See Section 6 on page 43 for sensor installation instructions Table 3 Suggestions for Preventing T...

Page 16: ...14 Getting Started...

Page 17: ...s not allowed In all cases the local authority having jurisdiction shall have a final say DANGER Il est interdit de proc der toute installation ou configuration d un d bitm tre qui n est pas explicite...

Page 18: ...SSEMBLY IF THE ELECTRICAL PARAMETERS OF THE CABLE ARE UNKNOWN THE FOLLOWING DEFAULT VALUES MAY BE USED 1 CANADIAN ELECTRIC CODE C22 1 94 SECTION 18 AND ANSI ISA RP 12 6 TABLE 1 D C B A A B C D 1 2 3 4...

Page 19: ...RIETARY REPRODUCED OR DISCLOSED TO ANYONE WITHOUT TOLERANCING PER ANSI Y14 5 1994 TITLE 911 FLASH CONV DIRECT PERMISSION FROM HACH COMPANY ANYTHING WHETHER OR NOT SHOWN HEREON WHOLE OR IN PART BE USED...

Page 20: ...LOSED TO ANYONE WITHOUT DIRECT PERMISSION ANSI Y14 5M 1994 MATERIAL DRAWN ENGINEER DATE NAME TITLE SIZE B DWG NO REV WEIGHT SCALE 1 1 UNLESS OTHERWISE SPECIFIED G S DUKART S DUKART 12 8 2005 DIAGRAM S...

Page 21: ...nf METER INDUCTANCE 1 uh METER 2 WIRING METHODS MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ANSI NFPA 70 ARTICLE 504 CANADIAN ELECTRIC CODE C22 1 94 SECTION 18 AND ANSI ISA RP 12 6 3 FOR M...

Page 22: ...R DEFINABLE LENGTH 1 IF THE ELECTRICAL PARAMETERS OF THE CABLE ARE UNKNOWN THE FOLLOWING DEFAULT VALUES MAY BE USED CANADIAN ELECTRIC CODE C22 1 94 SECTION 18 AND ANSI ISA RP 12 6 3 FOR MODEM INSTALLA...

Page 23: ...RIETARY REPRODUCED OR DISCLOSED TO ANYONE WITHOUT TOLERANCING PER ANSI Y14 5 1994 TITLE 940 FLASH CONV DIRECT PERMISSION FROM HACH COMPANY ANYTHING WHETHER OR NOT SHOWN HEREON WHOLE OR IN PART BE USED...

Page 24: ...2 3 4 5 6 7 8 8 7 6 5 4 3 2 1 INTERPRET GEOMETRIC TOLERANCING PER ANSI Y14 5M 1994 MATERIAL DRAWN ENGINEER DATE NAME TITLE SIZE B DWG NO REV WEIGHT SCALE 1 1 UNLESS OTHERWISE SPECIFIED E S DUKART S D...

Page 25: ...CAL PARAMETERS OF THE CABLE ARE UNKNOWN THE FOLLOWING DEFAULT VALUES MAY BE USED CANADIAN ELECTRIC CODE C22 1 94 SECTION 18 AND ANSI ISA RP 12 6 3 FOR MODEM INSTALLATION IN CONDUIT MINIMUM CONDUIT DIA...

Page 26: ...NKNOWN THE FOLLOWING DEFAULT VALUES MAY BE USED CANADIAN ELECTRIC CODE C22 1 94 SECTION 18 AND ANSI ISA RP 12 6 3 FOR MODEM INSTALLATION IN CONDUIT MINIMUM CONDUIT DIAMETER IS 1 2 IN 1 3 CM MINIMUM BE...

Page 27: ...P N 4741 75 KHz ZERO DEADBAND PROBE 4741 100 FT MAX 5233 05 100 FT MAX CUSTOMER DEFINABLE LENGTH 3 FOR MODEM INSTALLATION IN CONDUIT MINIMUM CONDUIT DIAMETER IS 1 2 IN 1 3 cm MINIMUM BEND RADIUS IS 3...

Page 28: ...NKNOWN THE FOLLOWING DEFAULT VALUES MAY BE USED CANADIAN ELECTRIC CODE C22 1 94 SECTION 18 AND ANSI ISA RP 12 6 3 FOR MODEM INSTALLATION IN CONDUIT MINIMUM CONDUIT DIAMETER IS 1 2 IN 1 3 CM MINIMUM BE...

Page 29: ...5 100 FT MAX CUSTOMER DEFINABLE LENGTH 1 IF THE ELECTRICAL PARAMETERS OF THE CABLE ARE UNKNOWN THE FOLLOWING DEFAULT VALUES MAY BE USED CANADIAN ELECTRIC CODE C22 1 94 SECTION 18 AND ANSI ISA RP 12 6...

Page 30: ...RE UNKNOWN THE FOLLOWING DEFAULT VALUES MAY BE USED 1 CANADIAN ELECTRIC CODE C22 1 94 SECTION 18 AND ANSI ISA RP 12 6 CAPACITANCE 2 nf METER INDUCTANCE 1 uh METER 2 WIRING METHODS MUST BE IN ACCORDANC...

Page 31: ...ep into the instrument Refer to Figure 14 on page 29 When not in use cover the connectors with their protective caps to prevent corrosion Use the appropriate manhole support bracket spanner bar See Re...

Page 32: ...p 2 Lift the end cap off 3 Remove the two thumbscrews securing the battery retaining plate and unlatch the two rubber hold down straps 4 Place the battery pack Cat No 6608500 inside the battery compar...

Page 33: ...s dans un environnement dangereux The entire battery assembly unscrews and separates to access the battery connector Cat No 5160 01 Follow the steps below to install the battery pack in the 911 1 Hold...

Page 34: ...e moisture When the blue desiccant turns pink replace the desiccant 4 3 4 Estimating the Battery Life When using the battery pack battery life is based on Number of sensors installed more sensors decr...

Page 35: ...un incendie ou une explosion DANGER Never install remove or charge batteries in a hazardous location DANGER Vous ne devez jamais installer retirer ou recharger les batteries dans un environnement dan...

Page 36: ...staller retirer ou recharger les batteries dans un environnement dangereux To recharge the 911 Lithium Ion Battery Pack 5160 01 1 Move the 911 Flow Meter to a non hazardous location 2 Remove the batte...

Page 37: ...icates with a PC via an optically isolated interface Figure 19 on page 35 The Opto Isolated Interface Cat No 4087 is used only for data downloading and remote programming This interface isolates the e...

Page 38: ...V dc Output current is 100 mA dc max with a duration of 500 ms D Sampler Start Black Used to wake up a wastewater sampler when a level and or rainfall set point condition is met so that it can begin...

Page 39: ...nule la fois la garantie et l agr ment de s curit intrins que du d bitm tre et peut provoquer un incendie ou une explosion Reportez vous aux sch mas de contr le de l installation The optional sampler...

Page 40: ...ule la fois la garantie et l agr ment de s curit intrins que du d bitm tre et peut provoquer un incendie ou une explosion Reportez vous aux sch mas de contr le de l installation The Optically Isolated...

Page 41: ...from the Optically Isolated Sampler Interface 2 Disconnect all the wires from the terminals labeled J4 through J6 Do not remove the wires from terminals labeled J1 through J3 3 Loosen the compression...

Page 42: ...40 Meter Installation...

Page 43: ...zed flow monitoring jobs Flo Center Integrated Sewer System Management Software provides high end automated data collection and automated batch report processing using an unlimited number of meters Mo...

Page 44: ...42 Software and Communications...

Page 45: ...of the liquid on the flow stream After measuring the level the microprocessor converts the level reading to a flow rate based on the user defined characteristics of the primary device 6 1 1 Installing...

Page 46: ...so that the entire beam falls within the channel and does not strike any obstructions Beam Width Formulas The maximum beam width for a given distance from the sensor can be calculated as follows Refe...

Page 47: ...racket Always level the sensor using a level The maximum water level must be below the deadband to ensure accurate readings Table 8 Beam Angle Spread by Distance Distance from Target in 75 KHz Beam Wi...

Page 48: ...Figure 24 Permanent Bracket and Isolation Washers 1 Wall Rail Mount Bracket Cat No 2974 3 Downlook Ultrasonic Sensor 2 Isolation Washers Cat No 6820 4 1 inch x 0 25 Hex Nuts Cat No 1429 1 2 3 4 This...

Page 49: ...5 25 inches Cat No 3046 5 14 cm 5 5 in tall Cat No 3108 3 16 625 inches 2 Cat No 3048 6 Horizontal and vertical sections are fully adjustable2 1 Sensor Mounting Clamp with built in bubble level Sensor...

Page 50: ...s problem Check for excessive foam and oil While the 940 Flow Meter is designed with an AGC Automatic Gain Control scheme to reduce these factors it is recommended that sites without these anomalies b...

Page 51: ...nimized Figure 27 on page 50 Mount the sensor 46 cm 18 in away from obstructions located in front of the in pipe sensor to prevent inaccurate liquid level readings Figure 26 Level the sensor using the...

Page 52: ...ommended calibration method use the sensor height method only when Liquid Depth calibration is not an option An Invisible Range can also be set which allows the transducer to ignore reflections from o...

Page 53: ...tom of the sensor to the zero flow point Add 18 3 cm 7 2 in to the measured distance to obtain the total zero flow distance Enter the total zero flow distance value into the application software 6 2 3...

Page 54: ...o not install more than one sensor at a time in pipes less than 61 cm 24 inches Multiple sensors in smaller pipes can create turbulent or accelerated flows near the sensors that may cause inaccurate m...

Page 55: ...pre drilled holes for direct mounting of the sensor to the band 2 Route the cable along the edge of the band and fasten the cable to the mounting band with nylon wire ties Figure 29 on page 54 to red...

Page 56: ...te flow meter manual Slide the mounting band as far as possible into the pipe to eliminate drawdown effects near the end of the pipe Locate the sensor at the bottom most point in the channel If excess...

Page 57: ...55 Sensor Installation Figure 31 Placing the Sensor into the Flow Velocity Sensor Downstream Position Manhole Velocity Sensor Upstream Position Normal Manhole...

Page 58: ...56 Sensor Installation...

Page 59: ...e 17 on page 32 and Figure 18 on page 32 prevents moisture damage to the batteries and power circuitry Table 9 contains replacement part numbers If the normally blue desiccant beads turn pink replace...

Page 60: ...and require no maintenance There are no other user serviceable components inside the electronics compartment 7 6 2 Memory Batteries An internal battery is provided to power RAM memory as well as the r...

Page 61: ...es The batteries need to be changed once a year due to the limited shelf life of any type of battery 1 Remove the cover from the RS232 interface Figure 32 2 Remove the old batteries Install fresh batt...

Page 62: ...rmanently damages the sensor Refer to Table 11 for acceptable cleaning solutions 2 Remove the screws from the protective cover Figure 33 and Figure 34 on page 61 3 Remove the cover and gasket 4 Swirl...

Page 63: ...Sensor 1 Screws 6 32 x 5 16 4 Pressure Transducer 2 Protective Cover 5 Sensor 3 Gasket Figure 34 Removing the Protective Cover Oil filled Sensor 1 Screws 6 32 x 5 16 4 Gasket 2 Protective Cover 5 Pres...

Page 64: ...e set screw 7 Insert the syringe tip slowly into the set screw hole and dispense the oil Figure 37 on page 63 Note While dispensing the oil hold the probe at an angle to allow the air to be pushed out...

Page 65: ...be replaced immediately Important Note When the beads begin to turn pink replace or recondition the beads Permanent damage to the sensor may occur if the desiccant is not maintained Never operate the...

Page 66: ...ilter is probably torn Replace the filter If the desiccant beads are completely saturated with water or the filter has been saturated with water or grease replace the filter Note If the filter needs t...

Page 67: ...the tape into the threads until it conforms to the shape of the threads 4 Place a new filter over the hole Make sure that the smooth side of the filter faces the inside of the canister 5 Place the th...

Page 68: ...66 Maintenance...

Page 69: ...ensor 0 10 ft range 75 ft cable with connector 88064 075 I S Oil Filled Submerged AV Sensor 0 10 ft range 100 ft cable with connector 88064 100 I S Oil Filled Submerged AV Sensor 0 30 ft range 30 ft c...

Page 70: ...o 12 in Pipes 6 inches 4021 8 inches 4022 10 inches 4023 12 inches 4024 In Pipe Sensor Mounting Bands for 15 to 42 in Pipes 15 inches 9706100 18 inches 9706200 21 inches 9706300 24 inches 9706400 24 i...

Page 71: ...69 Replacement Parts and Accessories 8 5 Mounting Plate Hardware for Directly Mounting to Pipe Wall Sensor Type Part Number Submerged Pressure 4939 In Pipe 3875...

Page 72: ...70 Replacement Parts and Accessories...

Page 73: ...Customer Service Department 1 800 368 2723 and get a Service Request Number SRN and shipping label 4 Use the shipping label provided and ship the equipment in the original packaging if possible Note D...

Page 74: ...www flow tronic com For France Spain and Great Britain France HACH LANGE FRANCE S A S 33 Rue du Ballon 93165 Noisy le Grand Telephone 33 0 1 48 15 68 70 Fax 33 0 1 48 15 80 00 Email info hach lange fr...

Page 75: ...aused by any repair or attempted repair not authorized by Hach Company Any product not used in accordance with the instructions furnished by Hach Company Freight charges to return merchandise to Hach...

Page 76: ...74...

Page 77: ...of the weir bottom of the V and the submerged sensor is 4 in 10 cm The distance between the surface of the water and the submerged sensor is 6 in 15 cm The level of water which is contributing to flow...

Page 78: ...aaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaa aaa...

Page 79: ...Devices Figure 41 Parshall Flume A Length of Converging Section 2 3A Length to Stilling Well Stilling Well Optional FLOW Submerged Probe Submerged Probe Submerged Flow Free Flow Head Measurement Poin...

Page 80: ...tegral Approach FLOW FLOW Submerged Probe Preferred Head Measurement Point Preferred Head Measurement Point D Conduit Diameter 2 Lower Transition Throat Water Surface Small jump should occur here Uppe...

Page 81: ...Preferred Head Measurement Point Water Surface Small jump should occur here FLOW FLOW Submerged Probe Preferred Head Measurement Point Lower Transition Throat Upper Transition Upstream Depth Downstrea...

Page 82: ...mary Devices Figure 44 H Flume FLOW FLOW Pipe Stub Inlet Bulkhead Approach Section H W T 4 1 3 2 Head Measurement Section Elevation View Top View Figure 45 Round Pipes FLOW Q FLOW Q Elevation View Top...

Page 83: ...50 show how to install the 911 and 940 Flow Meters in various applications Figure 46 shows Model 911 installed in a manhole with a single level velocity sensor stored in the small diameter pipe Figure...

Page 84: ...eters do not require profiling to establish average velocity allowing setup in a dry channel Figure 47 Rapid signal processing and temperature compensation accurately record the change from dry to wet...

Page 85: ...8 shows a storm vault accepting flow from two locations The 940 Flow Meter monitors level velocity and flow in both pipes and sends data via modem to a central location Figure 48 Installation for Mult...

Page 86: ...nt the 940 Flow Meter can measure depth and velocity in the primary channel and measure discharge in the overflow channel See Figure 49 In some instances the overflow in some CSO applications may be t...

Page 87: ...hain of custody In Figure 50 the 940 Flow Meter provides ultrasonic measurement of flow in a Parshall flume while also measuring flow upstream using the Continuity Equation Q AV This ensures no loss o...

Page 88: ...86 Channel Installation Options...

Page 89: ...ED indicator turns off Temperature At higher temperatures the electrical capacity that can be taken out of a battery increases At lower temperatures the electrical capacity that can be taken out of a...

Page 90: ...charger with the Lithium Ion battery pack DANGER The use of chargers other than those provided by the manufacturer for use with these batteries is not recommended and may damage the battery or shorte...

Page 91: ...sources of any kind To maximize battery life operate the battery at an ambient temperature of 20 C 70 F The permissible operating temperature range is 15 to 50 C 5 to 120 F Use in the 5 to 35 C 47 to...

Page 92: ...90 Batteries and Chargers...

Page 93: ...a slave 940 The 940 is always considered the slave never a master The master can address individual 940 Flow Meters or can broadcast a message to instruments within its scope Responses are never retu...

Page 94: ...field of an ASCII message frame consists of two ASCII characters that provide an additional level of error checking to verify the integrity of the communication media The LRC field is one byte that co...

Page 95: ...13 Modbus ASCII Memory Input Output Referencing System Reference Indicator Reference Type Meaning 0xxxx Discrete Output or Coil Binary 1xxxx Discrete Input Binary 3xxxx Input Register Real 4xxxx Outp...

Page 96: ...7 Cond Temp Integer 16 1 00 3C 40061 Level 2 Integer 16 1 00 3C 40061 Velocity 2 Integer 16 1 00 3E 40063 Flow 1 Integer 16 1 00 41 40066 1 The addresses shown above return a code that represents the...

Page 97: ...08 to obtain the level information which requires two registers to store the floating point value Note that registers are referenced from zero in the data field CFM 17 DEGREE_F 42 CFH 18 MILS 43 CFD 1...

Page 98: ...potential communication lag For example in a Wonderware application running a Modbus ASCII DDE server the COM port reply time out must be set to 12 seconds This is the amount of time that the meter i...

Page 99: ...point value is represented by two data words Because a single Modicon register consists of one word or 2 bytes two consecutive Modicon registers are needed to store one floating point value The repres...

Page 100: ...chneider Automation Modicon ladder logic block library user guide North Andover MA AEG Schneider Automation Inc 1996 D 16 Troubleshooting Tips Problem 940 Flow Meter responds to some Modbus messages b...

Page 101: ...eck the Modbus mode There are two different forms of Modbus ASCII and RTU Currently the 940 Flow Meter only support Modbus ASCII Consequently the device communicating with the meter must be set up for...

Page 102: ...e values as Integers If the server or MMI is formatting this data as any data type other than Integer the values will not be read or displayed correctly Different Modbus servers and MMI manufacturers...

Page 103: ...Installation Requirements 8 Intrinsically Safe Wiring Practices 9 Invisible Range 43 L Ladder Rungs 43 Lead Acid Gel Cell 87 M Maintenance 57 Memory Batteries 58 Multiple Source Monitoring at a Single...

Reviews: