1-7
Follow the steps below to load a patch file:
To do…
Use the command…
Remarks
Enter system view
system-view
—
Load the patch file from the
flash to the memory patch area
patch load
Required
Activating Patches
After you activate a patch, the patch will take effect and is in the test-run stage. After the switch is reset
or rebooted, the patch becomes invalid.
If you find that an ACTIVE patch is of some problem, you can reboot the switch to deactivate the patch,
so as to avoid a series of running faults resulting from patch error.
Follow the steps below to activate patches:
To do…
Use the command…
Remarks
Enter system view
system-view
—
Activate the specified patches
patch active patch-number
Required
Confirming Running Patches
After you confirm the running of a patch, the patch state becomes RUNNING, and the patch is in the
normal running stage. After the switch is reset or rebooted, the patch is still valid.
Follow the steps below to confirm the running of the patches:
To do…
Use the command…
Remarks
Enter system view
system-view
—
Confirm the running of the
specified patches
patch run patch-number
Required
This operation is applicable to patches in the ACTIVE state only.
One-Step Patch Uninstallation
z
On a centralized device
You can use the
undo patch install
command to uninstall all patches. The patches then turn to the
IDLE state. This equals execution of the commands
patch deactive
and
patch delete
.
z
On a distributed device
Summary of Contents for S5500-SI Series
Page 161: ...3 10 GigabitEthernet1 0 1 2 MANUAL...
Page 220: ...1 7 Clearing ARP entries from the ARP table may cause communication failures...
Page 331: ...1 7 1 1 ms 1 ms 1 ms 1 1 6 1 2 1 ms 1 ms 1 ms 1 1 4 1 3 1 ms 1 ms 1 ms 1 1 2 2 Trace complete...
Page 493: ...2 8...
Page 1111: ...1 10 Installing patches Installation completed and patches will continue to run after reboot...