Expert Sensor Box 7211/7212

Configuration

Configuration - Sensors

2.2.4

Choose sensor port: Selects a type of sensor to configure it. The first digit "1" indicates the number of
the sensor port (only important for devices with more than one sensor port). This is followed by the sen-
sor name (eg 7002 for the hybrid sensor), a letter for the sub-type sensor and the changeable sensor
name. The sensor subtypes are defined as: "T" = temperature, "H" = humidity, "I" = sensor input.

Sensor Name: Changeable name for this sensor. Temperature and humidity can have different names,
even if they are from the same sensor.

Generate messages: Enables the generation of messages.

Maximum/Minimum value: Here you can choose whether, and at what Maximum/Minimum temperature
or humidity measurements limits the alerts are send via SNMP traps, syslog or email.

Hysteresis: This is the distance between the value that is signaling an overrun of a limit and the value
that signals an underrun of the same limit.

Min/Max measurement period: Selects the time range for the sensor min / max values ?

?

on the overview

web page.

Hysteresis Example:

A Hysteresis value prevents that too much messages are generated, when a sensor value is jittering
around a sensor limit. The following example shows the behavior for a temperature sensor and a hyste-
resis value of "1". An upper limit of "50 °C" is set.

Example:

49.9 °C - is below the upper limit
50.0 °C - a message is generated for reaching the upper limit
50.1 °C - is above the upper limit
...

Summary of Contents for Expert Sensor Box 7211

Page 1: ...Expert Sensor Box 7211 7212 2015 Gude Analog und Digitalsysteme GmbH Manual Ver 2 2 0 valid from Firmware Ver 1 0 1 ...

Page 2: ...rver and rack environment like sensor values max min energy consumption as well as state of inputs and outputs with watchdog functions In particular connected consumers can be switched remotely with Gude Control Gude Control is available for the Expert Power Control 8220 8225 series and can be free downloaded from the Google Play Store and iTunes Store Have your Gude devices always in view and in ...

Page 3: ...hnical Specifications Chapter 2 Configuration 7 8 2 1 Configuration by Software 8 2 2 Configuration via Webinterface 2 2 1 Configuration IP Address 9 2 2 2 Configuration IP ACL 10 2 2 3 Configuration HTTP 11 2 2 4 Configuration Sensors 12 2 2 5 Configuration Alarm Beeper 13 2 2 6 Configuration SNMP 13 2 2 7 Configuration Syslog 14 2 2 8 Configuration E Mail 15 Chapter 3 Protocols 15 15 3 1 SNMP 16...

Page 4: ... the device without our permission Please note the safety advises and manuals of connected devices too The device is NOT a toy It has to be used or stored out or range of children Care about packaging material Plastics has to be stored out of range of children Please recycle the packaging materials In case of further questions about installation operation or usage of the device which are not clear...

Page 5: ...nected to the Ethernet orange Device is connected to the Ethernet TCP IP settings are not allocated green Device is connected to the Ethernet TCP IP settings allocated periodic blinking Device is in Bootloader mode Bootloader Mode 1 6 Certain actions can for safety reasons only be carried out if the device is in bootloader mode The fol lowing operations are possible only in Bootloader Mode Firmwar...

Page 6: ...te of the power or output ports as long as the supply voltage is maintained Abandonment of the Bootloader Mode via push button Hold both buttons for 3 seconds only if the device has 2 buttons or Remove and connect the power supply without operating a button by Software Start GBL_Conf exe Do a network search with the Search menu action In menu Program Device activate the item Enter Firmware Factory...

Page 7: ... an outdated browser cache Not always helps a Ctrl F5 it is recommen ded that you manually delete the cache in the browser options Alternatively you can test start the browser in private mode Technical Specifications 1 8 Interfaces 1 x Ethernet port RJ45 1 x Connector for AC Adaptor Network connectivity 10 100 MBit s 10baseT Ethernet Protocols TCP IP HTTP SNMP v1 und v2c SNMP traps Syslog E Mail S...

Page 8: ...GBL_Conf exe start the program and choose All Devices in the Search menu From the list select the appropriate device The lower part of the left half of the window now shows the current network settings of the device If the IP address is displayed with the default settings 192 168 0 2 either no DHCP server is present on the network or there could be no free IP address assigned to it Activate the Bo...

Page 9: ...in the network IP Address The IP address of the device Netmask The network mask used in the network Gateway address The IP address of the gateway Use DHCP Select yes if the TCP IP settings should be obtained directly from the DHCP server When the function is selected each time the device powers up it is checked if a DHCP server is availa ble on the network If not the last used TCP IP setting will ...

Page 10: ...riate servers and clients are registered in the IP access control list IP Access Control List The IP Access Control List ACL IP is a filter for incoming IP packets If the filter is active you can on ly connect to hosts and subnets whose IP addresses are entered in the list Examples Entry in the IP ACL Meaning 192 168 0 123 the PC with IP Address 192 168 0 123 can access the device 192 168 0 1 24 a...

Page 11: ...TP password If desired a http password protection can be enabled In this case an admin password and a user password can be assigned The password can have up to 15 characters User can log in by entering the user s password to query the status information and make changes to ports if applicable Admins have the privileges of a User and can change the Configuration settings In the username field of th...

Page 12: ...f messages Maximum Minimum value Here you can choose whether and at what Maximum Minimum temperature or humidity measurements limits the alerts are send via SNMP traps syslog or email Hysteresis This is the distance between the value that is signaling an overrun of a limit and the value that signals an underrun of the same limit Min Max measurement period Selects the time range for the sensor min ...

Page 13: ...mit inclusive hysteresis range Configuration Alarm Beeper 2 2 5 Enable Beeper The unit has an internal beeper that can be enabled for audible alarms Ampere Limit Enter the limit for the current at which the beeper is to be activated Configuration SNMP 2 2 6 SNMP get Enables the acceptance of SNMP GET commands Community public The community password for SNMP GET requests SNMP set Enables the accept...

Page 14: ...NMP v1 format SNMP v2c SNMP traps are sent in SNMP v2c format SNMP trap receiver You can insert here up to eight SNMP trap receiver More information about SNMP settings are available from our support or can be found on the Internet at www gude info wiki Configuration Syslog 2 2 7 Enable Syslog Enables the usage of Syslog Messages Syslog Server If you have enabled Syslog Messages enter the IP addre...

Page 15: ... Trying 212 227 15 129 Connected to smtp 1und1 com Escape character is 220 smtp 1und1 com mreu3 Welcome to Nemesis ESMTP server EHLO localhost TYPE THIS 250 smtp 1und1 com 250 STARTTLS 250 AUTH LOGIN PLAIN PLAIN SUPPORTED 250 AUTH LOGIN PLAIN 250 SIZE 120000000 250 HELP Protocols 3 SNMP 3 1 SNMP can be used to obtain status information via UDP port 161 Supported SNMP commands are GET GETNEXT GETBU...

Page 16: ...ding of the max min values of attached sensors Syslog 3 2 Syslog messages are simple text messages that are sent via UDP to a syslog server Under Linux normally a syslog daemon is already running eg syslog ng for Microsoft Windows systems some freeware programs are available on the market The syslog messages are sent for the following events Turning on the device Enable disable of syslog in the co...

Page 17: ... EMC 2011 65 EU zur Beschränkung der Verwendung bestimmter gefährlicher Stoffe in Elek tro und Elektronikgeräten RoHS on the restriction of the use of certain hazardous substances in electrical and electronic equipment RoHS und dass die nachstehenden harmonisierten Europäischen Normen zur Anwendung gelangt sind and comply with the following harmonised European standards EN 55022 2010 AC 2011 Einri...

Page 18: ...Expert Sensor Box 7211 7212 2015 Gude Analog und Digitalsysteme GmbH 12 17 2015 ...

Reviews: