8
Expert Power Control 1100/1101
Configuration
4.3
Configuration via webinterface
Go to the website of Expert Power Control 1100/1101. Enter the IP address of Expert Power Control 1100/1101 into the
address line of your internet browser:
http://”IP address of Expert Power Control 1100/1101”/
and press LOGIN.
To enter the configuration menu, click on „Configuration“ on the upper left side of the screen.
4.3.1
Configuration - Power Ports
4.3.1.1
Label
A name with a maximum of 15 characters can be entered here for each Power Port.
4.3.1.2
Initialization Status
Here can be the status of the Power Ports defined, that should be attained after the device has been turned on (remember
last state, on, off).
4.3.1.3
Initialization Delay
When the Power Port Initialization is executed after powering up of the device, a delay in the Initialization sequence can be
specified. This will prevent to turn on too much load at the same time. The delay can last up to 8191 seconds. This
corresponds to about two hours and 20 minutes.
4.3.1.4
Repower Delay
When this feature is enabled (value greater than zero), the power port will turn itself on after the specified time. This happens
after the power port was turned off via webinterface, SNMP or serial interface.