63
Expert Net Control 2304
© 2021 GUDE Systems GmbH
Specifications
Sensor Examples
a) External Sensors
>extsensor all show
E=1,L="7106",0="21.3°C",1="35.1%",3="1013hPa",4="5.2°C",5="16.0°C""
E=2,L="7102",0="21.2°C",1="35.4%",4="5.3°C",5="15.9°C""
The command lists one connected external sensor per line, and the individual meas-
ured values are separated by commas after the label name. The digit before the equal
sign corresponds to the Index field in the External Sensor Table.
>extsensor 1 0 value show
Displays temperature of the sensor at Port 1
b) Line Sensors
>linesensor all "0,1,2,3,12" show
L=1,L="Power Port",0="13000Wh",1="0W",2="225V",3="0A",12="998218s"
L=2,L="Power Port",0="13000Wh",1="0W",2="223V",3="0A",12="996199s"
This command outputs all line sensor values in one line. A list of all fields (according to
the energy sensor table) is transferred as parameter. In this example these are the
fields Absolute Active Energy (0), Power Active (1), Voltage (2), Current (3) and Reset
Time (12).
>linesensor 1
"0,1,2,3,12"
show
>linesensor 1 1 show
These variants give the sensor values of the field list or of a sensor at Line-In 1.
For devices with Overvoltage Protection, the "linesensor all" command also outputs
the state of the protection ("OVP=x"). A "1" means ok, a "0" a failure of the protection.
c) Port Sensors
>portsensor all "0,1,2,3,12" show
P=1,L="Power Port",0="13000Wh",1="0W",2="225V",3="0A",12="998218s"
P=2,L="Power Port",0="13000Wh",1="0W",2="225V",3="0A",12="996199s"
...
P=12,L="Power Port",0="13000Wh",1="0W",2="225V",3="0A",12="998218s"
This command outputs all port sensor values in one line. A list of all fields (according to
the energy sensor table) is passed as parameter. In this example these are the fields
Absolute Active Energy (0), Power Active (1), Voltage (2), Current (3) and Reset Time
(12).
>portsensor 2
"0,1,2,3,12"
show
>portsensor 2 1 show
These variants give the sensor values of the field list or a sensor to at Outlet Port 2.
d) Displaying Port Relays
>port all state 1 show
P1=ON,P2=OFF,P3=ON,P4=OFF,P5=OFF,P6=OFF,P7=OFF,P8=ON
The command "port all state {MODE0=0|MODE1=1|MODE2=2} show" returns the
switching state of all relays in 3 possible formats.
Summary of Contents for Expert Net Control 2304
Page 1: ...Manual Expert Net Control 2304 2021 GUDE Systems GmbH Manual Ver 1 0 0 from Firmware Ver 1 0 ...
Page 2: ...2 Expert Net Control 2304 2021 GUDE Systems GmbH ...
Page 5: ...Device Description ...
Page 12: ...12 Expert Net Control 2304 2021 GUDE Systems GmbH Device Description ...
Page 13: ...Operating ...
Page 23: ...Configuration ...
Page 50: ...Specifications ...
Page 81: ...Support ...