60
Expert Sensor Box 7213/7214
© 2022 GUDE Systems GmbH
Specifications
External Sensor Type Table "{7x01=0|7x02=1|7x03=2}"
Index
Description
Products
0
Temperature
7001, 7101, 7201
1
Temperature, Humidity
7002, 7102, 7202
2
Temperature, Humidity, Air Pressure
7003, 7103, 7203
External Sensor Field Table "{sen_field}"
Index
Description
Unit
0
Temperature
°C
1
Humidity
%
2
Digital Input
bool
3
Air Pressure
hPa
4
Dew Point
°C
5
Dew Point Temperature Difference
°C
4.6.2
Device MIB 7214
Below is a table of all device-specific OID 's which can be accessed via SNMP. In the
numerical representation of the OID the prefix " 1.3.6.1.4.1.28507 " (Gude Enterprise
OID) was omitted at each entry in the table to preserve space. The example for a com-
plete OID would be "1.3.6.1.4.1.28507.61.1.1.1.1". A distinction is made in SNMP OID 's
in between tables and scalars. OID scalar have the extension ".0" and only specify a
value. In SNMP tables the "x" is replaced by an index (1 or greater) to address a value
from the table.
Name
OID
Type
Acc.
Description
esb7214TrapCtrl
.67.1.1.1.1.0
Integer32
RW
0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
esb7214TrapIPIndex
.67.1.1.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each receiver slot.
esb7214TrapAddr
.67.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can
optionally be specified: 'name:port' An empty string disables this slot.
esb7214portNumber
.67.1.3.1.1.0
Integer32
RO
The number of Relay Ports
esb7214PortIndex
.67.1.3.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each Relay Port.
esb7214PortName
.67.1.3.1.2.1.2.x
OCTETS
RW
A textual string containing name of a Relay Port.
esb7214PortState
.67.1.3.1.2.1.3.x
INTEGER
RW
current state of a Relay Port
esb7214PortSw itchCount
.67.1.3.1.2.1.4.x
Integer32
RO
The total number of sw itch actions ocurred on a Relay Port. Does not
count sw itch commands w hich w ill not sw itch the ralay state, so just
real relay sw itches are displayed here.
esb7214PortStartupMode
.67.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
esb7214PortStartupDelay
.67.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
esb7214PortRepow erTime
.67.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repow er port after sw itching off