64
Expert Power Control 8221/8226
© 2022 GUDE Systems GmbH
Specifications
actual air pressure
epc8221Dew Point
.56.1.6.1.1.6.x
Integer32
RO
dew point for actual temperature and humidity
epc8221Dew PointDiff
.56.1.6.1.1.7.x
Integer32
RO
difference betw een dew point and actual temperature (Temp -
Dew Point)
epc8221ExtSensorName
.56.1.6.1.1.32.x
OCTETS
RW
A textual string containing name of a external Sensor
4.6.2
Device MIB 8226
Below is a table of all device-specific OID 's which can be accessed via SNMP. In the
numerical representation of the OID the prefix " 1.3.6.1.4.1.28507 " (Gude Enterprise
OID) was omitted at each entry in the table to preserve space. The example for a com-
plete OID would be "1.3.6.1.4.1.28507.58.1.1.1.1". A distinction is made in SNMP OID 's
in between tables and scalars. OID scalar have the extension ".0" and only specify a
value. In SNMP tables the "x" is replaced by an index (1 or greater) to address a value
from the table.
Name
OID
Type
Acc.
Description
epc8226TrapCtrl
.58.1.1.1.1.0
Integer32
RW
0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
epc8226TrapIPIndex
.58.1.1.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each receiver slot.
epc8226TrapAddr
.58.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can
optionally be specified: 'name:port' An empty string disables this slot.
epc8226portNumber
.58.1.3.1.1.0
Integer32
RO
The number of Relay Ports
epc8226PortIndex
.58.1.3.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each Relay Port.
epc8226PortName
.58.1.3.1.2.1.2.x
OCTETS
RW
A textual string containing name of a Relay Port.
epc8226PortState
.58.1.3.1.2.1.3.x
INTEGER
RW
current state of a Relay Port
epc8226PortSw itchCount
.58.1.3.1.2.1.4.x
Integer32
RO
The total number of sw itch actions ocurred on a Relay Port. Does not
count sw itch commands w hich w ill not sw itch the ralay state, so just
real relay sw itches are displayed here.
epc8226PortStartupMode
.58.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
epc8226PortStartupDelay
.58.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
epc8226PortRepow erTime
.58.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repow er port after sw itching off
epc8226PortResetDuration
.58.1.3.1.2.1.8.x
Integer32
RW
Delay in sec for turning Port on again after Reset action
epc8226Buzzer
.58.1.3.10.0
Integer32
RW
turn Buzzer on and off
epc8226ActivePow erChan
.58.1.5.1.1.0
Unsigned32
RO
Number of suppported Pow er Channels.
epc8226Pow erIndex
.58.1.5.1.2.1.1.x
Integer32
RO
Index of Pow er Channel entries
epc8226ChanStatus
.58.1.5.1.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
epc8226AbsEnergyActive
.58.1.5.1.2.1.3.x
Gauge32
RO
Absolute Active Energy counter.
epc8226Pow erActive
.58.1.5.1.2.1.4.x
Integer32
RO
Active Pow er