62
Expert Power Control 8041/8045
© 2022 GUDE Systems GmbH
Specifications
So later you can use the 'subtree names' instead of OIDs:
Name:
snmpwalk -v2c -mALL -c public 192.168.1.232 gudeads
OID:
snmpwalk -v2c -mALL -c public 192.168.1.232 1.3.6.1.4.1.28507
NET-SNMP Examples
Query Power Port 1 switching state:
snmpget -v2c -mALL -c public 192.168.1.232 epc822XPortState.1
Switch on Power Port 1:
snmpset -v2c -mALL -c private 192.168.1.232 epc822XPortState.1 integer 1
4.6.1
Device MIB 8041
Below is a table of all device-specific OID 's which can be accessed via SNMP. In the
numerical representation of the OID the prefix " 1.3.6.1.4.1.28507 " (Gude Enterprise
OID) was omitted at each entry in the table to preserve space. The example for a com-
plete OID would be "1.3.6.1.4.1.28507.85.1.1.1.1". A distinction is made in SNMP OID 's
in between tables and scalars. OID scalar have the extension ".0" and only specify a
value. In SNMP tables the "x" is replaced by an index (1 or greater) to address a value
from the table.
Name
OID
Type
Acc.
Description
epc8041TrapCtrl
.85.1.1.1.1.0
Integer32
RW
0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
epc8041TrapIPIndex
.85.1.1.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each receiver slot.
epc8041TrapAddr
.85.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can
optionally be specified: 'name:port' An empty string disables this slot.
epc8041portNumber
.85.1.3.1.1.0
Integer32
RO
The number of Relay Ports
epc8041PortIndex
.85.1.3.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each Relay Port.
epc8041PortName
.85.1.3.1.2.1.2.x
OCTETS
RW
A textual string containing name of a Relay Port.
epc8041PortState
.85.1.3.1.2.1.3.x
INTEGER
RW
current state of a Relay Port
epc8041PortSw itchCount
.85.1.3.1.2.1.4.x
Integer32
RO
The total number of sw itch actions ocurred on a Relay Port. Does not
count sw itch commands w hich w ill not sw itch the ralay state, so just
real relay sw itches are displayed here.
epc8041PortStartupMode
.85.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
epc8041PortStartupDelay
.85.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
epc8041PortRepow erTime
.85.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repow er port after sw itching off
epc8041PortResetDuration
.85.1.3.1.2.1.8.x
Integer32
RW
Delay in sec for turning Port on again after Reset action
epc8041Buzzer
.85.1.3.10.0
Integer32
RW
turn Buzzer on and off