Expert PDU Energy 8340/8341
© 2021 GUDE Systems GmbH
Specifications
difference between dew point and actual temperature (Temp -
DewPoint)
pdu8340ExtSensorName
.54.1.6.1.1.32.x
OCTETS
RW
A textual string containing name of a external Sensor
4.6.2
Device MIB 8341
Below is a table of all device-specific OID 's which can be accessed via SNMP. In the
numerical representation of the OID the prefix " 1.3.6.1.4.1.28507 " (Gude Enterprise
OID) was omitted at each entry in the table to preserve space. The example for a com-
plete OID would be "1.3.6.1.4.1.28507.65.1.1.1.1". A distinction is made in SNMP OID
's in between tables and scalars. OID scalar have the extension ".0" and only specify a
value. In SNMP tables the "x" is replaced by an index (1 or greater) to address a value
from the table.
Name
OID
Type
Acc.
Description
pdu8341TrapCtrl
.65.1.1.1.1.0
Integer32
RW
0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
pdu8341TrapIPIndex
.65.1.1.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each receiver slot.
pdu8341TrapAddr
.65.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can
optionally be specified: 'name:port' An empty string disables this slot.
pdu8341Buzzer
.65.1.3.10.0
Integer32
RW
turn Buzzer on and off
pdu8341ActivePowerChan
.65.1.5.1.1.0
Unsigned32
RO
Number of suppported Power Channels.
pdu8341PowerIndex
.65.1.5.1.2.1.1.x
Integer32
RO
Index of Power Channel entries
pdu8341ChanStatus
.65.1.5.1.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
pdu8341AbsEnergyActive
.65.1.5.1.2.1.3.x
Unsigned32
RO
Absolute Active Energy counter.
pdu8341PowerActive
.65.1.5.1.2.1.4.x
Integer32
RO
Active Power
pdu8341Current
.65.1.5.1.2.1.5.x
Unsigned32
RO
Actual Current on Power Channel.
pdu8341Voltage
.65.1.5.1.2.1.6.x
Unsigned32
RO
Actual Voltage on Power Channel
pdu8341Frequency
.65.1.5.1.2.1.7.x
Unsigned32
RO
Frequency of Power Channel
pdu8341PowerFactor
.65.1.5.1.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
pdu8341Pangle
.65.1.5.1.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
pdu8341PowerApparent
.65.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
pdu8341PowerReactive
.65.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
pdu8341AbsEnergyReactive
.65.1.5.1.2.1.12.x
Unsigned32
RO
Absolute Reactive Energy counter.
pdu8341AbsEnergyActiveResettab
le
.65.1.5.1.2.1.13.x
Unsigned32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all
resettable counter.
pdu8341AbsEnergyReactiveResett
able
.65.1.5.1.2.1.14.x
Unsigned32
RO
Resettable Absolute Reactive Energy counter.
pdu8341ResetTime
.65.1.5.1.2.1.15.x
Unsigned32
RO
Time in seconds since last Energy Counter reset.
pdu8341ForwEnergyActive
.65.1.5.1.2.1.16.x
Unsigned32
RO
Forward Active Energy counter.
pdu8341ForwEnergyReactive
.65.1.5.1.2.1.17.x
Unsigned32
RO
Forward Reactive Energy counter.
pdu8341ForwEnergyActiveResetta
ble
.65.1.5.1.2.1.18.x
Unsigned32
RO
Resettable Forward Active Energy counter.
Summary of Contents for Expert PDU Energy 8340 Series
Page 2: ...2 Expert PDU Energy 8340 8341 2021 GUDE Systems GmbH...
Page 5: ...Device Description...
Page 12: ...12 Expert PDU Energy 8340 8341 2021 GUDE Systems GmbH Device Description...
Page 13: ...Operating...
Page 21: ...Configuration...
Page 43: ...Specifications...
Page 76: ...Support...