Operation
Electrical safety devices, safety measures and earthing
7.3.2
Protection against overcurrent
On generators with factory-installed switch box, the power sockets are to be
protected against overcurrent and short circuits at the attached switch box
using line circuit breakers.
Line circuit breaker block
(protection: 3P + N)
Fig. 26 Miniature circuit breakers in the switch box
(only for generators 8kVA and 13 kVA)
Generators without factory-installed switch boxes
To protect the circuits (power sockets) connected to the generator, install
suitable safety devices in a separate switch cabinet.
y
Short circuit tripping characteristics: “B” characteristic
y
Protection against overcurrent: as per nominal current
y
The neutral conductor N must be secured.