Chapter 6 Specification of Parameters GK600 User Manual
- 202 -
Parameter copy fault "CPy"
Software version compatibility failure "SFt"
CPU interference fault "CPU"
Reference protection "oCr"
5V power supply out-of-limit "SP1"
Undervoltage protection "LoU"
PID feedback loss ”Plo”
2) Please use automatic fault reset function with caution, or fault will be extended.
E1-11
Relay action on drive fault
Range: 000~111
Factory default:
010
Ones place: when undervoltage fault occurs
0: No action
1: Action enabled
Set whether or not fault relay acts when undervoltage occurs.
Tens place: when fault locked
0: No action
1: Action enabled
Set whether or not the relay acts when the fault locked at latest power loss after power up.
Hundred's place: at interval of auto- reset
0: No action
1: Action enabled
Set whether or not the relay acts when fault occurs in automatic reset status.
E1-12
Cooling fan control
Range: 0~1
Factory default: 0
0: Auto run
The fans run all the time during the running. Determine if the fans continue to run or stop
according to module temperature after stop.
1: Always run after power up
The fans run all the time after applying power to the drive.
E1-13
Drive overheat alarm
threshold
Range: 0.0
℃
~100.0
℃
Factory default:
80.0
℃
This parameter sets the threshold of drive overheat alarm.
Group F Application
Group F0 Process PID
The purpose of process PID control is to make feedback value consistent with the set value.
PID control diagram is shown as Fig. 6-48.