background image

 

30309466                                                                          1                                                                                      Issue 2.10

 

                                       

 

Features 

  With  sandwich  structure, it is easy to be installed 

between DZ-03 base and a detector. 

  Three working modes settable (Mode I, II, III, and 

the latter two available with pre-alarm state). 

  16 tones of sound and bright flashing light. 

  Electronically  addressed.  The  address  and  tones 

can be modified in field. 

Description 

I-9406 Addressable Flashing Beacon Base is installed 

in field to warn people for evacuation with audible and 

visual alarm in case of a confirmed fire. 

The flashing beacon base can communicate with fire 

alarm  control  panel  (FACP)  through  a  built-in 

microprocessor.  On  receiving  a  start  command  from 

the FACP, the microprocessor will control the buzzer to 

generate  the  pre-set  fire  alarm  sound  and  light  the 

bright LED.

 

Wiring and Connection 

Terminals  of  the flashing beacon  base  are  shown in 

Fig. 1. 

A

B

61mm

41.3mm

 

Fig. 1   

Z1(1), Z2(3): Signal loop of FACP, polarity-insensitive.   

Recommended Wiring 

1.0mm

2

 or above fire cable, subject to local codes. 

Installation 

Warning:  Before  installing  the  flashing  beacon 

base, disconnect power from the loop and verify 

that all the bases are securely fixed and that the 

wiring is correct on each base. 

1  Before  installation,  make  sure  the  enclosure  is 

free  from  scratch  or  distortion,  and  labels  are 

complete. 

2  Installation schematic of the flashing beacon base 

is shown in Fig. 2. 

3  Secure  the  detector base (Fig.  4)  with  2  tapping 

screws,  and  wire  them  properly.  Align  the 

orientation mark B on the flashing beacon base to 

mark C of detector base,  and rotate the flashing 

beacon base clockwise to D. Refer to Fig. 3 and 4. 

4  If the  flashing  beacon  base comes  with  a  cover, 

align the orientation mark on the cover to mark A 

of the flashing beacon base (Fig.1), and rotate the 

cover clockwise to B. If it's used as detector base, 

remove the cover and install the detector on it with 

the same method. 

Electric Box

Flashing Beacon Base

Base

Cover or Detector

 

Fig. 2   

 

 

B

           

C

D

 

  Fig. 3 Flashing Beacon Base    Fig. 4 Detector Base 

Application 

The flashing beacon base can be used as the base of 

intelligent  heat  and  smoke  detectors  to  combine 

detection  and  alarm  in  a  single  device.  It  can  be 

connected  to  the  loop  of  FACP  without  additional 

power supply. 

Working Mode Setup and Tone Selection

 

The flashing beacon base has three working modes. 

The factory default is tone 14, mode I.   

The flashing beacon base has 16 tones, the setup of 

which also decides the setup of working modes. 

  If the flashing  beacon base is set with one of the 

tones from No. 1 to 16, it works in Mode I. 

  If it is set with one of the tones from No. 17 to 32, it 

works in Mode II. 

  If it is set with one of the tones from No. 33 to 48, it 

works in Mode III. 

  Tone 1~16, 17~32 and tone 33~48 are completely 

the same by  one-to-one correspondence, with the 

only  difference  that  they  work  in  different  modes. 

Please refer to the table of tones. 

Working Modes: 

Mode 

Address 

Type of fire alarm 

I

 

Single address, 

occupying one loop 

point 

Note: Detector & 

beacon base must 

have different 

addresses. 

Standalone. The 

beacon base gives 

alarm signal when 

started. 

II

Dual addresses, 

sharing high address 

with detector 

The beacon base 

gives pre-alarm 

signal when starting 

the higher address 

and alarm signal 

when starting the 

lower address. 

III 

Occupying dual 

addresses 

individually 

The beacon base 

gives pre-alarm 

signal when starting 

the lower address 

and alarm signal 

when starting the 

higer address. 

 

I-9406

 

Addressable Flashing Beacon Base

 

0832-CPD-2100

 

548e/03 

Reviews: