GST I-9333 Quick Start Manual Download Page 1

 

30303486                                                                                                       

           

                                                        Issue 3.04

 

                                       

 

 

Features 

  Fault checking on the power. 

  Cable checking on the intrinsically safe loop. 

  Metal  cabinet,  high  water-proof  and  anti-interference 

abilities. 

 

“S”,  “G”  can  activate  sounder/sounder  strobe 
externally. 

Description 

I-9333  Interface  can  connect  with  C-9404(Ex)  Sounder 
and  C-9403(Ex)  Sounder  Strobe  in  explosion-proof 
system.  Receiving  the  start  command  from  fire  alarm 
control  panel  or  the  closed  contact  signal  from 

“S”,  “G”, 

I-9333  Interface  will  activate  explosion-proof  devices  in 
field and transmits the action information to the fire alarm 
control panel. 
When 24VDC power fault or connection fault between the 
interface and field sounder or sounder strobe occurs, it will 
send fault signal to fire alarm control panel and illuminate 
Fault LED. 
Built-in safety barrier, it is  a relative  device  to restrict  the 
energy to the explosive environment. 

Connection and Wiring 

Cable Size 

The  1.0mm

or  above  intrinsically  safe  cable  is  used  to 

connect 

safety 

barrier 

and 

explosion 

proof 

sounder/sounder  strobe,  the  capacitance  distributed 
among  cables  should  not  be  ove

r  0.083

μ F,

  and  the 

inductance distributed should not be over 

4mH.

 The color 

of cables should be different to distinct polarity.   

1.0mm

2

  or  above  copper  cable  with 

φ 8mm

φ 10mm 

outer diameter for Z1, Z2, D1, D2, S, and G. 
φ 8mm

φ 10mm cable should be adopted in the places 

requiring water-proof. If twisted pair or solid wire has to be 
used,  twine  thread  seal  tape  around  the  cable  going 
through the Cable Entry to 

φ 8mm

φ 10mm. 

Terminals 

“Intrinsically  safe”  side  includes  terminal  3(+),  4(-)  of 
safety  barrier.  3(+)  connects  with  D1  of  explosion  proof 
sounder/sounder  strobe,  and  4(-)  connects  with  D2. 
Please note polarity.   

Note:  Must  connect  the  wire  correctly  otherwise  the 
interface won

’t alarm.   

“Non  intrinsically  safe”  side  include  six  terminals.  Z1,  Z2 
connects  with  the  polarity-insensitive  loop  of  fire  alarm 
control  panel,  D1,  D2  with  polarity-insensitive  24VDC 
power line and S, G with controlling input contact.   
In addition, the enclosure of the interface must connect to 
Ground securely, the bolt is as shown in Fig. 1. 

Installation 

Two mounting methods: One is mounted on the wall, and 
the other is mounted on the rack. 

a)  Wall  mounted:  Fix  the  mounting  bracket  to  the  wall 
using two M6×60 expansion bolts, its mounting dimension 
is shown in Fig. 2. 

b) Rack mounted: Remove the mounting bracket from the   

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig. 1 

back of the interface, then install the interface to the rack 
using M4

×

10 bolts, see Fig. 3.

 

Warning

This interface should be mounted in safety 

area. The wire of the interface from “Non-intrinsically 
safe”  and  those  from  “Intrinsically  safe”  should  be 
separated  from  each  other  and  be  kept  a  certain 
distance  (at  least  50mm).  Strictly  follow  the  relative 
explosion-proof code when installing.   

Waterproof Cap

Cable Entry

 

Fig. 2 

Wat

er

pr

oof C

ap

Rack

Cable

 Ent

ry

Cable

 Ent

ry

Cable

 Ent

ry

Fig. 3 

Note:  Horizontal  mounting  can  protect  water 
penetrating inside of the interface along the lead.

 

Application 

I-9333  Interface  can  connect  with  explosion-proof 
sounder/sounder strobe to form explosion-proof system in 
fire alarm system. Its wiring diagram is shown in Fig. 4.   

 

 

I-9333 Interface 

 

 

Bolt to Ground 

Cable Entry 

Cable Entry 