Features 

—

 Cable checking. 

—

 Occupying one address, this can be modified 

through P-9910B programmer or fire alarm control 
panel. 

—

  Power cut checking. 

—

 Two LEDs indicate fire and fault condition 

separately.  

—

 Plug-in structure. 

Description 

I-9319 Addressable Zone Monitor Unit (the unit) is 
designed to connect with conventional detectors, 
occupying one address. When any device in the loop 
reports fire signal, the unit will transmit the signal to the 
fire alarm control panel which generates fire alarm and 
displays the address of the unit. 

The end of the unit is connected with P-9907 Active 
End of Line Unit, if the output circuit is broken, the fault 
signal will be transmitted to the fire alarm control panel 
and then the address of the unit will be displayed on the 
fire alarm control panel. When a field device is removed, 
the unit will report fault without affecting normal 
operation of other field devices. 

Connection and Wiring 

Terminals of the unit are shown in Fig. 1.   

9

10

15

16

8

7

2

1

Z2

D2

Z1

D1

O-  O+

Mounting 
Hole

Mounting 
Hole

Mounting 
Direction

 

Fig. 1 

Z1, Z2: Connecting with control panel loop cable, 

polarity insensitive. 

D1, D2: Connecting with 24VDC, polarity insensitive. 
O-, O+: Polarity sensitive output.   

Recommended Wiring

   

1.0mm

2

 or above fire cable for each terminal, subject to 

local codes. The color of cables for O

-

 and O+ should 

be different. 

Installation 

The unit is simply plugged onto the base after 
corresponding terminals are connected. 

If the cable conduit is inside the wall, the base is 
installed onto the electric box (Fig. 2). If the cable 
conduit is on the surface of the wall, B-9310 Back Box 
is available (Fig. 3).   

 

 

 

 

Conduit

Electric 
Box

B-9310
Back Box

Conduit

the Unit

the Unit

Fig. 2                                                    Fig. 3 

Please note the upward arrow for mounting direction 
(Fig. 1). 

Application 

Address can be set in field through P-9910B 
programmer. The output loop can connect up to 15 
conventional devices. Detectors, such as C-9102 
Photoelectric Smoke Detector, C-9103 Rate of Rise and 
Fixed Temperature detector can be used together. 
1.  When the unit connects with conventional detector 
in series, the detector base should connect with an 
1N5819 diode, and P-9907 must be connected to the 
output end. P-9907 can also be used as the base of a 
conventional detector. System composition is shown in 
Fig. 4.

 

O-

O+

Diode

Diode

Conventional Detector

Conventional Detector

P-9907 Active End of Line Unit

A

d

d

e

s

s

a

b

le

 Z

o

n

e

 M

o

rn

it

o

U

n

it

I-

9

31

9

Fig. 4

 

2.  When P-9907 Active End of Line Unit is not used as 
detector base, a cover should be added, the system 
composition is shown as Fig. 5. 

The Intelligent Solution 

I-9319 

Addressable Zone Monitor Unit 