Features 

  A pair of input signals. Working mode can be set 

to  normally  open,  normally  closed  through 

P-9910B  programmer.  Input  signal  is  insulated 

from loop. 

  Two separate pairs of converting output contacts. 

  Occupying  one  address.  It  can  be  modified 

through a programmer or fire alarm control panel 

(FACP). 

  Monitoring power supply. 

  Plug-in structure. 

Description 

With  a  microprocessor,  I-9305  Voice  Alarm  Zone 

Control  Module  can  communicate  with  FACP, 

monitor  power  supply,  control  output,  indicator  and 

judge logic state of input signal. 

The  module  is  designed  to  switch  between  normal 

broadcasting  and  voice  alarm  broadcasting.  The 

module  can  switch  those  two  channels,  receive 

external 

answering 

signal 

and 

feed 

back 

automatically 

after 

switching 

to 

fire 

alarm 

broadcasting.  The  switching  is  successful  if  the 

relative  information  has  been  transmitted  to  fire 

alarm control panel.   

Connection and Cabling 

Fig. 1 shows terminals on the module. 

9

10

15

16

8

7

2

1

Mounting 
Hole

Mounting Hole

Mounting Direction

D1 D2

G

I1

Z1

Z2

SP1 XF1 ZC1 SP2 XF2 ZC2

65mm

Fig. 1

 

D1, D2: 24VDC power, non-polarized 

Z1, Z2: Connecting with loop of FACP, non-polarized 

I1, G: Volt-free input terminal 

ZC1, ZC2: Normal broadcasting input terminal 

XF1, XF2: Fire alarm broadcasting input terminal 

SP1, SP2: Output terminal connecting with speaker 

Recommended Cabling   

1.0mm

or  above  fire  cable  for  Z1,  Z2,  ZC1,  ZC2, 

XF1, XF2, SP1 and SP2. 1.5mm

or above fire cable 

for 24VDC power line, subject to local codes. 

Installation 

The  module  is  simply  plugged  onto  the  base  after 

corresponding terminals are connected. 

If  the  cable  conduit  is  inside  the  wall,  the  base  is 

installed  onto  the  Back  Box  (Fig.  2).  If  the  cable 

conduit  is  on  the  surface  of  the  wall,  B-9310  Back 

Box is available (Fig. 3).

 

Conduit

B-9310
Back Box

Conduit

Module

Module

Back Box

                 

Fig. 2                                            Fig. 3 

Note the upward arrow for mounting direction (Fig.1). 

Application 

Address  and  working  mode  can  be  set  in  field 

through  P-9910B  programmer,  please  refer  to 

P-9910B  Hand  Held  Programmer  Installation  and 

Operation Manual

 for specific operation. The working 

mode  of  module  is  defaulted  auto  feedback  (3), 

which  can  be  modified  to  normally  open  (4)  or 

normally closed (7) in field. 

The  module  can  be  connected  to  addressable  fire 

alarm broadcasting system, as shown in Fig. 4. 

 

I-9305   

Voice Alarm Zone Control Module 

 