30303027                                                                                 Issue 3.04

 

                                       

 

 

Features 

—

  Working mode can be set to normally open, 

normally closed and normally open cable monitor 
through programmer. 

—

  Electronically addressed. The address can be 

modified in field. 

—

 

The built-in microprocessor processes messages 
intelligently.  

—

  Insulation technology for input signal, good 

anti-interference ability.   

—

 Plug-in 

structure. 

Description 

I-9300 Addressable Input Module is designed to receive 
normally open or normally closed switch signal from fire 
devices with coincidence functions, and transmits these 
messages to fire alarm control panel (FACP) with 
coincidence detection function. When a device of this 
kind is activated, the module can send the output signal 
through signal loop to FACP to alarm or activate relative 
devices

.

   

Connection and Cabling 

Fig. 1 shows terminals on the module.   

9

10

15

16

8

7

2

1

Mounting 
Hole 

Mounting 
Hole
Mounting 
Direction

G

I1

Z1

Z2

GST-LD-8300/I-9300

65mm

 

Fig. 1   

Z1,Z2:Connecting with loop of FACP, 
polarity-insensitive. 
I1,G:Connecting with volt-free normally open contact 
(closed to activate and report alarm) of the device, it 
can be set to normally closed or normally open cable 
monitor.  

Recommended Cabling 

1.0mm

2

 or above fire cable for each terminal. Subject to 

local codes. 

Installation 

The module is simply plugged onto the base after 
corresponding terminals are connected.

 

If the cable conduit is inside the wall, the base is 
installed onto the Back Box (Fig. 2). If the cable conduit 
is on the surface of the wall, B-9310 Back Box is 
available. 

Note the upward arrow for mounting direction (Fig. 1).

 

 

 

 

              Fig. 2                                                  Fig. 3 

Application 

The module is designed to connect with active devices 
in field such as water flow switch, pressure switch, 
position switch, signal valve and devices able to 
transmit back switch signals.   

Address and working mode can be set through GST 
programmer, refer to 

P-9910B Hand Held Programmer 

Installation and Operation Manual

 for specific operation. 

Working mode is defaulted to normally open (4), while it 
can be modified to normally closed (7) or normally open 
cable monitor (1).

  

—

  Fig. 4 shows connecting the module with field 

device with volt-free normally open contact. Working 
mode is normally open (4).   

—

  Fig. 5 shows connecting the module with field 

device with volt-free normally closed contact. Working 
mode is normally closed (7).

 

—

  Fig. 6 shows connecting the module with field 

device with volt-free normally open contact requiring 
cable monitor. Working mode is normally cable monitor 
(1).

 

 

 

 

 

 

 

 

 

 

 

Fig. 4 

The Intelligent Solution

I-9300 

Addressable Input Module 

I-9300

Z1                                       Z2

                                                                        

I1                                        G

                                                                        

Normally Open Contact

          Field Device

Z1

Z2

Conduit

B-9310 
Back Box

Conduit

Module

Module

Back Box

 

548h/01