background image

 

30309459                                                   

     

                                             

                         

  Issue 1.06

 

                                       

 

Features 

        Fault self-diagnostic.   

 

A magnet test available. 

 

Providing for connections to remote indicators.   

 

Built-in microprocessor stores 14 history data. 

 

Polling LED can be set to OFF. 

 

Standard: UL268.

 

Description 

DI-M9102  Intelligent  Photoelectric  Smoke  Detector  (the  detector) 
can form fire alarm system connecting with a fire alarm control panel 
(FACP). The detector illuminates indicators to indicate fire condition 
and transmits alarm signals to the FACP.   

Using  infrared  scattering  technology,  with  an  innovative  chamber, 
the  detector  receives  very  weak  infrared  light  under  the  normal 
clean  environment.  If  smoke  particles  enter  the  chamber,  the 
received  light  signal  will  be  increased  by  scattering.  When  smoke 
density  reaches  a  certain  amount,  the  detector  will  give  alarm 
signals. In order to reduce interference and power consumption, the 
emitting circuit works in pulse mode to prolong the life of IR emitting 
diode..

 

Connection and Cabling 

The orientation base of DB-M01 is shown in Fig. 2. 

5

45

75

Cable Entry

Mounting
Hole

Fig. 1                                                          Fig. 2

 

Please install the base according to following steps: 

1) 

Locate  mounting  holes  on  the  rubber  layer  of  the  base 
according to the holes on the back box, and punch the holes 
with a screwdriver. 

2) 

Count  the  number  of  cables  needed  and  punch  correct 
quantity  of  holes  with  a  screwdriver  on  the  rubber  layer. 
Thread the cables through the cable entry holes.   

3) 

Install the base onto the back box with screws.   

Warning: Do not punch mounting holes and cable entry holes 
bigger than needed. Do not punch more holes than needed. 

Used together with UL certified GST-M200 control panel, loop of the 
control panel should be connected with 

terminals “1” and “3” of the 

base, polarity-insensitive; terminals 

“2” to anode of remote indicator 

and 

“4” to the cathode. System connection is shown in Fig 3. 

 

Remote Indicator

-

+

LOOP OUT

Addressable Detector

Remote Indicator

Addressable Detector

+

-

LOOP IN

 

Fig. 3 

Recommended Wiring 

1.0mm

or above fire cable for all, laid out through metal conduit or 

flame-resistant  conduit,  subject  to  local  codes.  The  connection  of 
remote indicator should use different color cables to distinct polarity.

 

 

 

 

Installation 

Refer to 

D Series Detector Application Bulletin 

for additional 

installation instructions

Fix  the  base  with  two  taping  screws.  Then  align  A  (Fig.  1)  on  the 
bottom  of  the  detector  to  B  (Fig.  2)  of  the  base,  and  rotate  the 
detector clockwise to mark C. Mounting of the detector is shown in 
Fig. 3.

 

54.5mm

Electrical Box

Conduit

Base

Detector

 

 

Fig. 4 

Application 

The polling LED is Normal by default, which can be modified to OFF 
state  using  P-9910B  programmer  changes  sensitivity  of  the 
detector.   

Program  sensitivity:  In  power-on  state,  input  unlocking  password 
and  press 

Clear

  to  unlock.  Press 

Function

,  then  press  “3”,  the 

screen shows “-” at the last digit. Input corresponding parameter of 
the  detector  and  press 

Program

,  the  screen  will  show  a  “P”,  the 

parameter is programmed successfully. Press 

Clear

 to clear the "P". 

Input locking password and press 

Clear

 to return.

 

Detectors Setup 

Input Parameter of a Detector 

Status of Polling LED 

Normal 

129 

OFF 

Read  sensitivity:  On  power-on  time,  press 

Test

,  the  LCD  screen 

shows  the  address  of  the  detector;  Press 

Up

,  it  shows  in  turn  the 

sensitivity level, device type, initial sensitivity. 

Testing 

Before  testing,  please  ensure  that  the  detector  has  been 
installed  correctly  and  powered  up.  After  10  seconds,  testing 
can begin.   

Before  testing,  notify  the  proper  authorities  that  the  system  is 
undergoing  maintenance  and  will  temporarily  be  out  of  service. 
Disable  the  zone  or  system  undergoing  maintenance  to  avoid 
unwanted alarms.

  

All  detectors  must  be  tested  after  installation  and  periodically 
thereafter.  Testing  methods  must  satisfy  the  Authority  Having 
Jurisdiction  (AHJ).  Detectors  offer  maximum  performance  when 
tested  and  maintained  in  compliance  with  NFPA  72.  The  detector 
can be tested in the following way:

 

1) 

Magnet test 

Magnetic test zone is shown in Fig.5. Put the magnet of commission 
tool close to the zone of the detector and hold on for a few seconds 

DI-M9102 Intelligent   

Photoelectric Smoke Detector

 

 

 

 

Reviews: