30308677 

                   

                                                                                                     

       

  Issue 1.03

 

                                       

 

Features 

 

Address programmable in field. 

 

Built-in MCU stores up to 14 history data.   

 

Combined  smoke  and  heat  algorithm  greatly     
improves optical sensitivity. 

 

Strong  environmental  adaptability  due  to  drift 
compensation. 

 

Self-diagnostic. 

 

Reed switch testing.   

 

Removable  innovative  sensing  chamber,  easy  for             
maintenance. 

 

Dirty chamber checking. 

 

 

Fire LED allows 360

°

viewing 

  Remote indicator output available.   

  3 levels sensitivities programmable; fix temperature 

or rate of rise programmable. 

Description 

DI-9101  Digital  Intelligent  Multi  Sensor  designed 
according  to  UL  268/UL  521,  integrates  photoelectric 
detection  and  fixed  temperature  and  rate  of  rise 
detection  technology  by  combining  smoke  sensor  and 
semi-conductor  heat sensor in mechanism and circuitry 
structure.  Just  because  of  the  combination  of  smoke 
detection  and  heat  detection,  it  not  only  overcomes  the 
disadvantage  that  detectors  using  common  infrared 
scattering technology are insensitive to black smoke with 
small particles, but also can pick up fire with obvious rise 
of temperature such as alcohol flame, thus extending its 
application range. 

Connection and Cabling 

Fig. 1 shows the detector bottom and Fig. 2 the base.

 

C

B

A

                   

Fig. 1                              Fig. 2 

There are four terminals with numbers on the base.   

1&3: Loop connection (polarity-insensitive) 
2: Positive terminal of remote indicator 
4: Negative terminal of remote indicator 

Recommended Cabling 

1.0mm

2

  or  above  fire  cable  is  recommended,  laid 

through metal or flame-retardant  conduit,  but  subject  to 
local codes.   

Note: Different color cables are used to avoid wiring 
mistake.

 

Installation 

A  fixed  installation  direction  is  ensured  by  the  location 
elements on the detector and the base. Fix the base with 
two  tapping  screws,  and  then  align  mark  A  on  the 
detector with  B on the base, rotate the detector to align 
mark A with mark C (Refer to Fig. 1 and 2 for the position 
of the marks), the detector will be fitted to the base. 
 
 
 
 
 
 

 

 

Fig. 3 shows the installation of the detector. 

Detector

Base

Conduit

Back Box

5

4.5m

m

 

Fig. 3 

Application

 

The detector can be addressed in field by using P-9910B 
programmer.  Please  refer  to 

P-9910B  Hand  Held 

Programmer  Installation  and  Operation  Manual

  for 

details. 
In  power-on  state,  input  unlocking  password  and  press 

Clear

  to  unlock.  Press 

Function

,  then  press  “3”,  the 

screen shows “-” at the last digit.   
Input  corresponding  sensitivity  or  parameter  and  press 

Program

, the screen will show a “P”, the corresponding 

sensitivity  or  parameter  is  programmed.  Press 

Clear

  to 

clear the "P". Input locking password and press 

Clear

 to 

return. 
Rate of rise and level 1 is defaulted.   

Parameters set using programmer 

Input Number   

Smoke Sensitivity 

Heat Sensitive   

Level 1 

Rate of rise 

Level 2 

Rate of rise 

Level 3 

Rate of rise 

11 

Level 1 

Fixed temperature 

12 

Level 2 

Fixed temperature 

13 

Level 3 

Fixed temperature 

Testing 

Before  testing,  please  ensure  that  the  detector  has 
been  installed  correctly  and  powered  up.  After  10 
seconds, testing begins.

 

1) The  detector  must  be  tested  after  installation  and 

periodical maintenance. 

2) Testing method 

a) 

Reed Switch Testing 

Magnetic  test  zone  is  shown  in  Fig.  4.  Put  the 
magnet  of  commission  tool  close  to  that  of  the 
detector  and  hold  on  for  a  few  seconds  until  the 
detector generates alarm. 

DI-9101   

Digital Intelligent Multi Sensor 