Features
Address programmable in field.
Built-in MCU stores up to 14 history data.
Combined smoke and heat algorithm greatly
improves optical sensitivity.
Strong environmental adaptability due to drift
compensation.
Self-diagnostic.
Reed switch testing.
Removable innovative sensing chamber, easy for
maintenance.
Dirty chamber checking.
Fire LED allows 360
°
viewing
Remote indicator output available.
3 levels sensitivities programmable; fix temperature
or rate of rise programmable.
Description
DI-9101 Digital Intelligent Multi Sensor designed
according to UL 268/UL 521, integrates photoelectric
detection and fixed temperature and rate of rise
detection technology by combining smoke sensor and
semi-conductor heat sensor in mechanism and circuitry
structure. Just because of the combination of smoke
detection and heat detection, it not only overcomes the
disadvantage that detectors using common infrared
scattering technology are insensitive to black smoke with
small particles, but also can pick up fire with obvious rise
of temperature such as alcohol flame, thus extending its
application range.
Connection and Cabling
Fig. 1 shows the detector bottom and Fig. 2 the base.
C
B
A
Fig. 1 Fig. 2
There are four terminals with numbers on the base.
1&3: Loop connection (polarity-insensitive)
2: Positive terminal of remote indicator
4: Negative terminal of remote indicator
Recommended Cabling
1.0mm
2
or above fire cable is recommended, laid
through metal or flame-retardant conduit, but subject to
local codes.
Note: Different color cables are used to avoid wiring
mistake.
Installation
A fixed installation direction is ensured by the location
elements on the detector and the base. Fix the base with
two tapping screws, and then align mark A on the
detector with B on the base, rotate the detector to align
mark A with mark C (Refer to Fig. 1 and 2 for the position
of the marks), the detector will be fitted to the base.
Fig. 3 shows the installation of the detector.
Detector
Base
Conduit
Back Box
5
4.5m
m
Fig. 3
Application
The detector can be addressed in field by using P-9910B
programmer. Please refer to
P-9910B Hand Held
Programmer Installation and Operation Manual
for
details.
In power-on state, input unlocking password and press
Clear
to unlock. Press
Function
, then press “3”, the
screen shows “-” at the last digit.
Input corresponding sensitivity or parameter and press
Program
, the screen will show a “P”, the corresponding
sensitivity or parameter is programmed. Press
Clear
to
clear the "P". Input locking password and press
Clear
to
return.
Rate of rise and level 1 is defaulted.
Parameters set using programmer
Input Number
Smoke Sensitivity
Heat Sensitive
1
Level 1
Rate of rise
2
Level 2
Rate of rise
3
Level 3
Rate of rise
11
Level 1
Fixed temperature
12
Level 2
Fixed temperature
13
Level 3
Fixed temperature
Testing
Before testing, please ensure that the detector has
been installed correctly and powered up. After 10
seconds, testing begins.
1) The detector must be tested after installation and
periodical maintenance.
2) Testing method
a)
Reed Switch Testing
Magnetic test zone is shown in Fig. 4. Put the
magnet of commission tool close to that of the
detector and hold on for a few seconds until the
detector generates alarm.
DI-9101
Digital Intelligent Multi Sensor