background image

 

30309767                                                                                                                                                                    Issue 1.04

 

                                       

 

 

Features 

 

High bright red LEDs are used as light source. 

 

Sound level: 85dB (A weighted, 3m in front). 

Description 

DC-9404(IS) Intrinsically Safe Conventional Sounder 
and  DC-9403(IS)  Intrinsically  Safe  Conventional 
Sounder 

Strobe 

(hereinafter 

called 

the 

sounder/sounder strobe) is a kind of audible/audible 
and visual alarm device used to warn people in field 

when fire occurs. It’s applicable to zone 1 and zone 2 
of  areas  with  explosion-proof  requirement  in 
petroleum and chemical industries. It can match with 
I-9333 Interface. 
Base with 25.5mm high are available.

 

Connection & Wiring 

Terminals on the base are shown in Fig. 2. 

  

 

5mm

55mm

80mm

Arch knock off Hole

G

1

K

1

D

D

2

1

2

Z

2

K

S

Z

Water leak hole

       

Fig. 1                                    Fig. 2

 

D1+  (9),  D2-  (7):  Connected  with  I-9333  Interface, 
polarized.   
Intrinsic  Safety  Parameters  for  D1/D2:

 

Ui=28V

Ii=93mA

Ci=0

Li=0

Pi=0.65W 

D1 is connected with (3) of the safety barrier and D2 
to (4). 

Recommended Wiring 

Intrinsically  safe  cable  with  cross  section  not  less 
than 1.5mm

2

, subject to local codes.

 

Installation 

Warning: Before installing the device, disconnect 
the power from the loop. 

 

Before  installation,  make  sure  the  enclosure  is 

in good condition and marking complete. 

 

When  the  sounder/sounder  strobe  is  surface 

mounted,  it  should  be  placed  0.2m  from  the  ceiling 
for normal space height. When conduit is embedded, 
the  base  can  be  mounted  on  the  electrical  box.   
Its  mounting  method  is  shown  in  Fig.  3.  Water  leak 
hold should installed downward. 

 
 

 

 

Conduit

Electrical Box

Wire hole

Water leak hole
should downward

 

         

Fig. 3 

 

The  base  and  the  sounder/sounder  strobe  are 

twisted  together.  When  mounting,  remove  the 
sounder  strobe,  thread  cables  through  the  cable 
entry  in  the  base  and  connect  with  corresponding 
terminals,  then  twist  the  sounder/sounder  strobe 
onto the base. 

 

If  the  sounder/sounder  strobe  is  required 

anti-removal, knock down the arch knock-off hole as 
shown  in  Fig.  1  and  fix  it  with  ST2.9

×

6.5  tapping 

screws (in this case, it must be removed by a special 
tool). 

Application 

The  sounder/sounder  strobe  can  match  I-9333 
Interface  to  form  an  intrinsically  safe  system.  The 
system wiring is shown in Fig. 4.

 

Non-intrinsincally Safe Loop

Intrinsincally Safe Loop

 D1   D2     Z1  Z2

I-9333 Circuit
Board

I-9333 Interface

24VDC

Fire Alarm Control Panel

L-

L+

2(-)

1(+)

GST-AS-200 Zener

   Safety Barrier

Safety Area

4(-)

3(+)

Hazardous Area

1

Z

2

Z

K

2

S

D

2

G

1

K

D

1

 

Fig. 4

 

 

DC-9404(IS)

 

Intrinsically Safe Conventional Sounder

   

DC-9403(IS) 

Intrinsically Safe Conventional Sounder Strobe

 

 

 