Features 

  2 classes programmable. 

  Self-diagnosis.   

  Reed switch testing. 

  The fire LED allows 360° viewing. 

  Output terminal for remote indicator available. 

  Complying with EN 54-5. 

Description 

DC-9103  Innovation  Dual  Heat  Detector  is  a  new  generation 
product  of  GST.  With  built-in  microprocessor,  it  works  stably  by 
being fixed with highly reliable fire judging program.   

On  detecting  a  fire  signal,  it  can  change  its  own  current  to 
transmit  the  signal  to  fire  alarm  control  panel  (FACP)  or 
addressable  zone  monitor  unit.  The  detector  keeps  illuminating 
fire LED until it is reset by power-down. 

 

Connection and Wiring 

The detector bottom is shown in Fig. 1 and the base in Fig. 2. 

C

B

A

 

Fig. 1                      Fig. 2

 

There are four terminals with numbers on the base. 

1: Detection zone positive IN 
2: Detection zone positive OUT 
3: Detection zone negative IN and OUT 

2: Positive terminal of remote indicator 
4: Negative terminal of remote indicator   

Recommended Wiring 

1.0mm

or  above  fire  cable  for  all  terminals  laid  through  metal 

conduit or flame retardant conduit, subject to local codes. 

Note:  It

’s recommended to use cables  of different colors to 

avoid incorrect wiring. 

Installation 

First fix the orientation base with two tapping screws. Then align 
A (Fig. 1) on the bottom of the detector to B (Fig. 2) of the base, 
and rotate the detector clockwise to mark C. 
Mounting of the detector is shown in Fig. 3. 

Detector

Base

Conduit

Electric Box

51.3mm

Fig. 3

 

Application 

Warning:  The  alarm  current  depends  on  the  current  limit  of 
the  FACP.  24VDC  power  cannot  be  applied  to  the  detector 
directly. Otherwise the detector may be damaged for lack  of 
current- limit resistor. 

The  default  class  of  the  detector  is  A1R,  which  can  be  modified 
using GST handheld programmer.   

 

 

 

When  the  programmer  is  in  standby  state,  entering  unlock 
password  and  pressing  “Clear”,  it  will  be  unlocked.  Pressing 

Function

 followed by 

4

, there will be a “-”at the last digit. Entering 

different number corresponding to the classes 

(“2” for A1R, “3” for 

A2S)  followed  by 

“Program”,  there  will  be  a  “P”  shown  on  the 

screen, indicating its class is programmed. Pressing 

“Clear” can 

clear the 

“P”, and entering locking password followed by “Clear” 

will exit. 

The detector is  especially  applicable to places where  fire  occurs 
with  a  sharp  rise  of  temperature.  Used  together  with  smoke 
detectors,  it  can  help  to  increase  the  reliability  of  fire  detection 
thus reducing losses. 

  When  the  detector  is  connected  with  compatible  FACP  or 

addressable  zone  monitor  unit  in  series,  if  DP-9907  Active 
End of Line Unit (AEOL) is connected to the end of output loop, 
a DB-01D base should be used.

 

  If  the  AEOL  is  used  as  the  detector  base,  a  conventional 

detector can  be installed  on it. The  system composition is 
shown in Fig. 4. 

 

Fig. 4

 

  When the AEOL is not used as the detector base,  a cover 

should  be  put  on  it.  The  system  composition  is  shown  in 
Fig. 5. 

  Fig. 5 

  When  the  detector  is  connected  with  conventional  FACP  or 

addressable zone monitor unit, if a 4.7k

Ω end of line resistor is 

connected to the end of output loop, DB-01 base is used. The 
system composition is shown in Fig. 6.   

 

Fig. 6

 

DC-9103   

Innovation Dual Heat Detector 