Features 

 

Sensitivities programmable. 

 

Strong 

environmental 

adaptability 

due 

to 

drift 

compensation. 

 

Integrated  algorithm  for  analyzing  fire,  improving  the 
sensitivity highly.   

 

Self-diagnostic. 

 

Reed switch testing. 

 

Removable  innovative  sensing  chamber,  easy  for 
maintenance. 

 

Reporting dirt fault for contaminated chamber. 

 

Fire LED allows 360

°

viewing. 

 

3-level sensitivities and fixed temperature or rate of rise 
programmable.   

Description 

DC-9101 (IS) Intrinsically Safe    Conventional    Combination 
Heat 

Photoelectric 

Smoke 

Detector 

(the 

detector), 

non-addressable, is a kind of combination detector consisting 
of  smoke  sensing  parts  and  semi-conductor  heat  sensing 

parts  in  technological  structure  and  circuit  structure.  It’s 
applicable to zone 1 and zone 2 of areas with explosion-proof 
requirement  in  petroleum  and  chemical  industries.  It  can 
match  with  fire  alarm  control  panel,  I-9332  Interface, 
explosion-proof detector and end-of-line resistor produced by 
GST  to  conduct  the  processing  of  detector  signals.  The 
detector  has  the  advantages  of  both  conventional 
photoelectric detector and rate of rise and fixed temperature 
heat  detector.  Just  because  of  the  combination  of  smoke 
detector  and  heat  detector,  it  overcomes  the  non-sensitivity 
to  dark  smoke  particles  of  ordinary  scattering  photoelectric 
detectors.  It  can  also  pick  up  fire  with  obvious  rise  of 
temperature  such  as  alcohol  flame,  thus  extending  the 
application range. 

Connection and Cabling 

Fig.1 shows the detector bottom and Fig. 2

 

the base. 

A

 

C

B

100mm

A

 

Fig. 1                                Fig. 2

 

There are four terminals with numbers on the base. 

1: Detection zone positive IN 
2: Detection zone positive OUT 
3: Detection zone negative IN and OUT 
4: No connection.

 

Recommended Cabling 

1.0mm

or  above  fire  cable.  The  capacitance  distributed 

among  cables  should  not  be  over  0.083

μF,  and  the 

inductance  distributed  should  not  be  over  4.1mH.  Laid  out 
through  metal  conduit  or  flame-retardant  conduit,  subject  to 
local codes.   

Installation

 

Fix the base with two tapping screws, and then align mark A 
on the detector bottom with B on the base, rotate the detector 
to  align  mark  A  with  mark  C  (Refer  to  Fig.  1  and  2  for  the 
position of the marks), the detector will be fitted to the base. 

 

 

Fig.3 shows the mounting of the detector. 

Detector

Base

Conduit

Back Box

 

Fig. 3 

Application 

Warning: The alarm current depends on the current limit 
of  the  control  panel.  24VDC  cannot  power  the  detector 
directly. Otherwise the detector will be blown up for lack 
of current limit resistor.

 

The sensitivity level 1 is defaulted, which can be modified by 
P-9910B  programmer.  Refer  to  P-9910B  Hand  Held 
Programmer Installation and Operation Manual for details. 
In power-on state, input unlocking password and press 

Clear

 

to unlock. Press 

Function

, then number 

“3”, the screen shows 

“-” at the last digit.   
Input  corresponding  sensitivity  or  parameter  and  press 

Program

,  the  screen  will  show  a  “P”,  the  corresponding 

sensitivity or parameter is programmed. Press 

Clear

 to clear 

the "P". Input locking password and press 

Clear

 to return. 

Rate of rise and level 1 is defaulted.   

Parameters set using programmer 

Input Number   

Smoke Sensitivity 

Heat Sensitive   

Level 1 

Rate of rise 

Level 2 

Rate of rise 

Level 3 

Rate of rise 

11 

Level 1 

Fixed temperature 

12 

Level 2 

Fixed temperature 

13 

Level 3 

Fixed temperature 

If the detector connects with fire alarm control panel, I-9332 
interface  and  other  exposition  proof  products  in  series,  a 
4.7k

Ω  end-of-line resistor should be connected to the end of 

loop. System connection is shown in Fig. 4. Note the polarity 
of power line.   

4

2

3

1

Zener 

B

a

rr

ie

r

O-

O+

Z2

Z1

D2

D1

Circuit 

B

o

ar

d

I2

I1

O1

O2

K2

K1

4       3      2       1

5        6      7        8

I- 9332 Interface 

Intrinsically Safe

 Detector

 Detector

Manual Call Point

End

 of

 line 

re

si

sto

r

4.

7k

Ω

Hazardous Area

Safety Area 

Intrinsically Safe

Intrinsically Safe

 Detector

Intrinsically Safe

 

        Fig. 4 

Testing 

Before testing, please ensure that the detector has been 
installed  correctly  and  powered  up.  After  10  seconds, 
testing begins.

 

1) The  detector  must  be  tested  after  installation  and 

periodical maintenance. 

DC-9101(IS) Intrinsically Safe 

Conventional Combination Heat Photoelectric Smoke Detector

 

 