Features 

 

Reusable button, that can be reset manually; 

 

Providing an independent output contact; 

 

Plug-in structure. 

Description 

C-9201 (Ex) Explosion Proof Manual Call Point (MCP) 
is  installed  in  public  places.  When  there  is  a  fire, 
pressing the nearest MCP, alarm signal can be sent to 
the  fire  alarm  control  panel  (FACP).  And  the  control 
panel  will  show  the  code  of  I-9332  Interface 
connecting with the MCP, and give alarm sound. 

The  MCP  is  operated  by  pressing  the  mechanically 
latched button to reduce possibility of accidental alarm. 
There is a LED on the MCP, which is used to indicate 
its status. 

Connection and Cabling 

Terminals of the MCP are shown in Fig.1. 

Cable 
Entry

Mounting 
Hole

Mounting 
Hole

65mm

 

Fig.1

 

Connection: 
I1,  I2:    Connecting  to  intrinsically  safe  side  of  the 
Safety Barrier 
K1, K2: Normally open output terminals 
O1, O2: Connecting to the next MCP 
Recommended Wiring: Selecting intrinsically safe cable 
with  cross  section  not  less  than  1.0mm

,  and  the 

capacity  assigned  among  cables  should  not  be  over 
0.04

μ F,  the  inductance  assigned  not  over  4.3mH.  All 

wiring  must  be  installed  in  compliance  with  the  local 
codes.   

 
 
 
 
 
 
 
 

 

 

Installation 

Unplug  the  MCP,  thread  the  cable  through  the  cable 
entry of the base box and connect it to corresponding 
terminals,  and  plug  the  MCP  back.  The  base  of  the 
MCP  can  be  surface  or  flush  mounted  as  shown  in 
Fig.2 and Fig.3. 
 

MCP

Conduit

Back Box

MCP

Back Box

Conduit

 

 

                Fig.2                           

   

              Fig.3 

 

Warning: Before installing the MCP, disconnect the 

power from the loop  and  verify  that all  bases  are 

securely  installed  and  that  the  wiring  polarity  is 

correct at each base. 

 

 

 

 

 

 

 

C-9201(Ex)   

Explosion Proof Manual Call Point

 

 