46 Smart Climate 310 rev. 03
Setting the 0-10V Fan Output's Timer
When the temperature decreases below the start temperature of
the 0-10V fan output, the fans of this output operate at their
minimum speed, according to a timer. The timer's On and Off times
can be adjusted from 0 to 900 seconds, in increments of 15
seconds.
To set the timer for the 0-10V fan output, proceed as follows:
1. Press
0-10v Output
.
Make sure the 0-10V is used for ventilation in the User Setup menu.
2. Press the down-arrow key to select the timer display.
3. Press
Adjust
. The On time flashes on the display. Use
the arrow keys to set it to the desired value.
4. Press
Adjust
once again, the Off time flashes on the
display. Use the arrow keys to set it to the desired
value.
Assigning T° Probes to the 0-10V Fan Output
The 0-10V fan output operates according to the average
temperature of a particular group of temperature probes. This
procedure shows how to choose the probes.
1. Press
0-10v Output
.
Make sure the 0-10V is used for ventilation in the User Setup menu.
2. Press the down-arrow key to select the probe selection
display.
3. Select which sensors are used to control the 0-10V
output.
NOTE:
Blinking digits represent probes that are assigned for
this purpose.
NOTE:
At least one temperature probe must be selected.
4. Press
Adjust
then set each probe's status with the
arrow keys.
Summary of Contents for Smart Climate 310
Page 1: ...Smart Climate 310 User s Guide 895 00676 REV 04 890 00582 REV 03...
Page 96: ...96 Smart Climate 310 rev 03 Probe Assignment...
Page 97: ...Smart Climate 310 rev 03 97 User Setup Menu...
Page 98: ...98 Smart Climate 310 rev 03...
Page 101: ...Smart Climate 310 rev 03 101 3 Press on the card and make it clip to the main board...
Page 102: ...102 Smart Climate 310 rev 03...