Smart Climate 310 rev. 03 39
Adjusting the Starting Temperature for Fan Stages
The first variable fan stage starts when the room temperature
reaches the temperature set point. You must specify a start
temperature for all other fan stages. Note that at least 0.5°F
(0.3°C) must be left between 2 consecutives stages.
NOTE:
The first fan stage performed by the controller is the
variable stage assigned for minimum ventilation, which is not
necessarily stage 1
NOTE:
The number of stages displayed in the following menu is
limited by the maximum fan stage selected at the beginning of
this section.
To adjust the starting temperature of fan stages, proceed as
follows:
1. Press
Stages
.
2. Press the down-arrow key in order to select the start
temperature of the 2
nd
fan stage (The number displayed on
screen refers to the stage number).
3. Press
Adjust
and then use the arrow keys to set the start
temperature to the desired value.
4. Press
Adjust
once again to validate.
5. Repeat steps 1 to 4 to set the start temperature of all fan
stages.