Chapter 9: Configuring a 0-5 Volt Zone Type
Resetting the Daily Minimum and Maximum
The system monitors and constantly updates the minimum and maximum values reached within a 24 hour
period. The time of the recorded minimum and maximum values is displayed. After 24 hours, the values
are reset and the monitoring starts anew.
In status mode, under the
General
tab in the zone you are configuring, click on the
Reset min/max
.
The information beside the
Max 24h
and
Min 24h
buttons is reset.
Setting the Alert Recognition Time
The alert recognition time is used to calculate the set period of time before an alert condition is recognized
and an alert set off. The zone must continuously be in an alert condition for a specific period of time before
an alert is recognized and set off.
1. In edit mode, under the
General
tab of the zone you are configuring, click on the edit field next to the
Recognition
button.
2. Set the alert recognition time.
Figure 9-2
Graph displaying an example of an alert with an 8 second recognition time
TEMPERA TURE
RECOGNITION TIME = 8 SECONDS
TIME
(SECONDS)
HIGH ALERT
THRESHOLD
INDOOR
T° READING
LOW ALERT
THRESHOLD
5
10
15
20
25
30
5 SECONDS
ABOVE HIGH
THRESHOLD
12 SECONDS AB OVE
HIGH THRESHOLD
ALERT SET OFF
AFTER 8 SECONDS
8 SECONDS
ALERT
NO ALERT
HIGH T° SETTING
LOW T° SETTING
Setting the Alert Recovery Time
The alert recovery time is a set amount of time that a zone must remain within its normal range following
an alert before a new alert can be set off.
1. In edit mode, under the
General
tab of the zone you are configuring, click on the edit field next to the
Recovery
button.
2. Set the alert recovery time.
895-00677
Agri Alert 128 Touch
59
Summary of Contents for 890-00584
Page 14: ...NOTES 14 895 00677 Agri Alert 128 Touch...
Page 20: ...NOTES 20 895 00677 Agri Alert 128 Touch...
Page 30: ...NOTES 30 895 00677 Agri Alert 128 Touch...
Page 38: ...NOTES 38 895 00677 Agri Alert 128 Touch...
Page 44: ...NOTES 44 895 00677 Agri Alert 128 Touch...
Page 64: ...Chapter 9 Configuring a 0 5 Volt Zone Type 64 895 00677 Agri Alert 128 Touch...
Page 66: ...NOTES 66 895 00677 Agri Alert 128 Touch...
Page 82: ...NOTES 82 895 00677 Agri Alert 128 Touch...
Page 88: ...NOTES 88 895 00677 Agri Alert 128 Touch...
Page 92: ...NOTES 92 895 00677 Agri Alert 128 Touch...
Page 96: ...NOTES 96 895 00677 Agri Alert 128 Touch...
Page 100: ...NOTES 100 895 00677 Agri Alert 128 Touch...
Page 102: ...NOTES 102 895 00677 Agri Alert 128 Touch...
Page 106: ...NOTES 106 895 00677 Agri Alert 128 Touch...
Page 107: ...F Wiring Diagram with Terminals 895 00677 Agri Alert 128 Touch 107...
Page 110: ...NOTES 110 895 00677 Agri Alert 128 Touch...
Page 118: ......