1.6 Chlorine rooms

Chlorine rooms are rooms, where a chlorine gas dosing system 
and/or chlorine containers are located. The chlorine in these 
rooms is under pressure.

1.6.1 Regulations for chlorine rooms

According to the German regulations for accident prevention 
"Chlorination of water", such rooms have to meet the following 
requirements:
• They should not have connections to other rooms, and must 

be separated gas-tight and fire-resistant.

• They must be at ground level, dry and air-conditioned. The 

recommended room temperature is 18-20 °C. It should be 
neither lower than 0 °C nor higher than 50 °C.

• Overpressure lines of dosing equipment must not end in the 

open air.

• Ventilation openings leading into the open air must be limited 

to 2 x 20 cm

2

.

• Appropriate exhaust devices with downstream absorption 

systems must be installed.

• Chlorine gas must not get into lower-lying rooms, shafts, pits, 

canals or aspirating holes of ventilation systems.

• Chlorine rooms must be equipped with a water sprinkling 

system to precipitate the escaping chlorine gas.

– The sprinkling system must have a run-off with air trap.
– Operation must be possible manually from outside the 

chlorine rooms.

• A chlorine gas warning system must be installed

– with optical and acoustical alarm device,
– with connection to the water sprinkling system,
– with a warning system that reactivates automatically after 

switch-off (e.g. for container exchange).

• The floor of a chlorine room must be even, the exit not below 

ground level and not higher than a possible loading ramp.

• Requirements of chlorine rooms
• Chlorine rooms must have a direct exit to the open air.
• Doors must be lockable, open outwards, and it must be 

possible to open the doors without a key from inside the room.

• Chlorine rooms must not be dedicated for the permanent stay 

of people.

• Eating, drinking, or storing food in chlorine rooms is 

prohibited.

1.6.2 Labelling of chlorine rooms

In Germany, according to DIN 4844, the following warning signs 
must be installed outside the entrance of a chlorine room:

Fig. 3

Warning sign and supplementary sign "Chlorination 
plant: Access only for instructed persons"

Inside a chlorine room, the mandatory sign "Use the gas mask" 
and the "Instruction sheet for first aid in case of chlorine gas 
intoxications" must be installed.

Fig. 4

Mandatory sign (DIN 4844)

TM

04

 07

04 

09

08

TM

04

 06

99

 09

08

TM

0

4

 0

7

01

 0

908

Summary of Contents for Vaccuperm VGA-111

Page 1: ...Vaccuperm VGA 111 Vacuum regulator Installation and operating instructions GRUNDFOS INSTRUCTIONS Other languages http net grundfos com qr i 95714202...

Page 2: ...rst aid in case of accidents 3 1 5 Handling chlorine containers 4 1 6 Chlorine rooms 5 2 Introduction 6 2 1 Correct usage 6 2 2 Inappropriate usage 6 2 3 Qualification of the users 6 2 4 Responsibilit...

Page 3: ...ive equipment Outside the chlorine rooms Well visible Easily available at any time Protected from dust and moisture 1 4 First aid in case of accidents 1 4 1 First aid after inhaling chlorine 1 Keep ca...

Page 4: ...atures over 50 C Transport containers only with valve protection nut and protective cap 1 5 4 Valid regulations In Germany the following regulations apply Regulations for accident prevention Chlorinat...

Page 5: ...ust have a run off with air trap Operation must be possible manually from outside the chlorine rooms A chlorine gas warning system must be installed with optical and acoustical alarm device with conne...

Page 6: ...ate protective clothing in accordance with national regulations for the prevention of accidents when operating the system and handling chemicals 2 4 Responsibilities of the operator The operator of th...

Page 7: ...n B Directly on the cylinder W Wall mounting C Header line BC Directly on the cylinder header line Connection 1 G 1 2 G 3 4 3 U S yoke 4 Copper pipe 6 8 mm Inlet valve B Basic S Short L Long 230 240 V...

Page 8: ...cal indication Weight Approx 2 4 kg according to the execution of the pressure connection Pressure gauge 0 16 bar with without limit contact for setting the minimum admission pressure Short inlet valv...

Page 9: ...t 34 05 C Density gas 3 214 g l at 0 C 1 bar 1 litre of liquid chlorine at 0 C is equivalent to 457 litres 0 457 m3 of chlorine gas 1 kg of liquid chlorine at 0 C is equivalent to 311 litres 0 311 m3...

Page 10: ...ich reduces the overpressure from the chlorine tank side to the negative pressure on the vacuum side The valve at the vacuum regulator opens when after switching on the injector a sufficient vacuum ha...

Page 11: ...ap are available for more safety Dosing regulator C The chlorine gas volume flow is adjusted with the dosing regulator This can be effected manually or automatically via motor control Injector D Injec...

Page 12: ...tions Max length m of the vacuum lines between vacuum regulator and dosing regulator Dosing quantity g h 40 100 250 500 1000 2000 4000 0 DN 8 DN 8 DN 8 DN 8 DN 8 DN 8 DN 10 10 DN 8 DN 8 DN 8 DN 8 DN 8...

Page 13: ...or 2 Overpressure line to the adsorption filter 3 Vacuum line from the vacuum regulator 4 Vacuum line to the injector Warning Replace the gaskets of the pressure connection at any change of container...

Page 14: ...se all chlorine container valves 2 Open container connection valves and all shut off valves up to the chlorine gas dosing system 3 Open the connection valve of the nitrogen cylinder 4 Slowly open the...

Page 15: ...the valves of full or empty chlorine containers with closing nut marked chlorine or Cl2 and gasket Stuck valves Stuck valves can be loosened by wrapping a cloth with warm water around the valve If thi...

Page 16: ...um regulator onto the chlorine container 13 Check the tightness as described in section 6 1 Checking the tightness 14 Re start the system 7 3 Switching off the chlorine gas dosing system 7 3 1 Emergen...

Page 17: ...tainer damaged Use another chlorine container d Pressure connection loose Tighten the pressure connection e Sealing surface at the pressure connection of the vacuum regulator damaged Call the service...

Page 18: ...kich PT Declara o de conformidade UE A Grundfos declara sob sua nica responsabilidade que os produtos VGA 111 VGA 113 VGA 117 VGA 146 VGB 103 VGS 141 VGS 143 VGS 145 VGS 147 VGS 148 aos quais diz resp...

Page 19: ...19 Declaration of conformity EAC 2 Vaccuperm 004 2011 010 2011 020 2011 TC RU C DK 30 01214 17 12 2019 153032 1 Vaccuperm 032 2013 TC N RU DK 30 05343 08 10 2020 1 2016 143581 188...

Page 20: ...20...

Page 21: ...ia S r l Via Gran Sasso 4 I 20060 Truccazzano Milano Tel 39 02 95838112 Telefax 39 02 95309290 95838461 Japan GRUNDFOS Pumps K K 1 2 3 Shin Miyakoda Kita ku Hamamatsu 431 2103 Japan Phone 81 53 428 47...

Page 22: ...splayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2019 Grundfos Holding A...

Reviews: