10. Setting the product
•
Press the button to select control mode and setting.
The LEDs will indicate the control mode. See table below.
A cycle is nine button presses.
The factory setting is zone pump, setting III.
LED
Control mode
TM082466
Zone pump, setting I
TM082467
Zone pump, setting II
TM082468
Zone pump, setting III (factory
setting)
TM082469
Zone valve, setting I
TM082471
Zone valve, setting II
TM082472
Zone valve, setting III
TM082473
TRV, setting I
TM082474
TRV, setting II
TM082475
TRV, setting III
10.1 Settings according to system type
System
Recommended control mode
TM083013
Zone pump system
Zone pump (constant curve)
TM083012
Zone valve system
Zone valve (constant pressure)
TM083015
TRV system
TRV (proportional pressure)
TM083014
Underfloor system
Zone valve (constant pressure)
TM083016
Boiler pump
Zone pump (constant curve)
When selecting a boiler pump,
there are many requirements
from the boiler manufacturer to,
for example, a minimum flow.
We recommend you to select
constant curve and one of the
three settings to give you the
corresponding flow per the boiler
requirement.
TM083017
Tank pump
Zone pump (constant curve)