English (GB)
27
12. Technical data
Supply voltage
1 x 230 V - 10 %/+ 6 %, 50/60 Hz.
Motor protection
The pump requires no external motor protection.
Enclosure class
IPX4D.
Relative air humidity
Maximum 95 %.
Ambient temperature
0 °C to +40 °C.
Temperature class
TF110 to EN 60335-2-51.
Liquid temperature
Maximum: +110 °C.
Continuously: +2 °C to +95 °C.
System pressure
The system pressure is indicated on the nameplate.
Inlet pressure
The following minimum pressures must be available
at the pump inlet during operation:
EMC (electromagnetic compatibility)
EN 61800-3.
Electromagnetic disturbance, first environment
(residential areas).
Immunity to electromagnetic disturbance, second
environment (industrial areas).
Sound pressure level
The sound pressure level of the pump is lower than
38 dB(A).
Leakage current
The pump mains filter will cause a discharge current
to earth during operation.
I
leakage
< 3.5 mA.
Inputs and outputs
13. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.
Ambient temperature
[°C]
Maximum liquid
temperature
[°C]
0 to 30
110
35 90
40 70
Pump type
System pressure
Number of
bolt holes
PN 6
PN 10
PN 16
[MPa]
[MPa]
[MPa]
UPE(D)
80-120 FZ
0.6 4
1.0 1.6
8
UPE
100-120 FZ
0.6 4
1.0 1.6
8
Pump type
Liquid temperature
75 °C
90 °C
110 °C
[bar]/
[MPa]
[bar]/
[MPa]
[bar]/
[MPa]
UPE(D) 80-120 FZ
0.6/
0.06
1.0/
0.1
1.7/
0.17
UPE 100-120 FZ
0.6/
0.06
1.0/
0.1
1.7/
0.17
Start/stop input
External potential-free switch.
Contact load:
5 V, 0.5 mA.
Screened cable.
Loop resistance:
Maximum 130
Ω
/km.
Logical levels:
Logical zero: U < 1.5 V.
Logical one: U > 4.0 V.
Min. curve input
Input for analog
0-10 V signal
External signal: 0-10 VDC.
Maximum load: 1 mA.
Screened cable.
Signal output
Internal potential-free change-
over contact.
Maximum load:
250 V, 2 A, AC1.
Minimum load: 5 V, 1 mA.
Screened cable.
Bus input
Grundfos bus protocol,
GENIbus protocol, RS-485.
Screened cable.
Lead cross section:
0.25 - 1 mm
2
.
Cable length:
Maximum 1200 m.
Subject to alterations.