8.5.3 Head and flow
Very low flows cannot be registered, and the R100
will show "<" in front of the lowest possible flow value
of the pump in question.
8.5.4 Speed
The actual pump speed.
8.5.5 Liquid temperature
The actual temperature of the pumped liquid.
8.5.6 Power input and power consumption
This display does not apply to UPE(D) 80-120 FZ
and UPE 100-120 FZ.
Actual power input and power consumption of the
pump.
Power consumption is not calculated in
UPE(D) 80-120 FZ and UPE 100-120 FZ.
8.5.7 Operating hours
Number of operating hours of the pump.
The value of operating hours is an accumulated
value and cannot be set to zero.
8.6 Menu INSTALLATION
In this menu, the settings are chosen that should be
considered when installing the pump.
8.6.1 Control mode
Description of function, see section
Select a control mode:
•
Prop. pressure (proportional pressure),
•
Const. pressure (constant pressure),
•
Const. curve (constant curve).
Setting of setpoint and curve is carried out in display
in the
OPERATION
menu.
8.6.2 Min. curve
This display does not apply to UPE(D) 80-120 FZ
and UPE 100-120 FZ.
Description of function, see section
In this display, it is possible to choose between two
min. curves. The curve is used when the operating
mode "Min. curve" is selected.
When controlling UPE(D) 80-120 FZ and
UPE 100-120 FZ, only one min. curve is available.
8.6.3 Temperature influence
Description of function, see section
.
The temperature influence function can be activated
in this display.
In the case of temperature influence, the pump must
be installed in the flow pipe. It is possible to choose
between maximum temperatures of 50 °C and 80 °C.
The temperature influence function will be active
only in proportional- or constant-pressure control
mode.
When the temperature influence is active, a small
thermometer is shown in the display "Setpoint" in the
OPERATION