Page 8

Multi Function Dial On Terminal Box

Offset Dial (When dip switch D is on)

The  Offset dial allows the user to fine tune the input
signal. The input signal may be varied plus or minus 1-
5%. This offset will affect the signal through it's entire
range.  The factory default is 0.  The offset setting
cannot increase the output to greater than 100% or less
than the selected minimum output of either 0% or 15%.

Example

:

The measured input signal is 2.1-10.1V and as a result
the pump does not shut off because the signal doesn't
drop to 2V. The dial is set to -5%
and the input signal is offset
down to 2.0-9.6V. The pump
will now shut off, however the
pump will not reach the full 10V
speed now, due to the offset.

Manual % Dial (When dip switch D is off)

The manual % dial allows the speed of the pump to be

manually adjusted and set by the user.  The speed of

the pump may be manually adjusted anywhere from

min to 100%, but once set remains fixed at that speed.

The "min" position on the dial will either be equal to

"OFF" or "15%" depending on the position of dip switch

C.  The factory default is 50%.

Performance Indicator LEDs (Fig. 7c)
Power ON

  (green)  indicates  power  is  applied.

% Out

(Yellow) indicates the speed of the pump by

flashing  at  different  rates.

Before You  Leave

Place this brochure, and all other brochures
relating to the installation, in a conspicuous
location near the control for future reference.

It is important to explain the operation of this
control within the system to the end user and to
anyone else who may be operating the system.

Page 8

Figure 7C -

  Performance

indicator LEDs

Figure 7B 

- % Offset

Offset /

Manual %

-5%

0

-1

-2

-3

-4

+1

+2

+3

+4

+5%

Min

100%

Multi Function Dial On Terminal Box:
Offset Dial (When dip switch D is ON)

The Offset dial allows the user to fine tune the input
signal.  The input signal may be varied plus or minus 1-
5%.  This offset will affect the signal through it’s entire
range.  The factory default is 0.  The offset setting
cannot increase the output to greater than 100% or less
than the selected minimum output of either 0% or 15%.

Example:

The measured input signal is 2.1-10.1V and as a result
the pump does not shut off because the signal doesn’t
drop to 2V.  The dial is set to -5%
and the input signal is offset
down to 2.0-9.6V.  The pump
will now shut off, however the
pump will not reach the full 10V
speed now, due to the offset.

Figure 6 - 

% Offset

Manual % Dial (When dip switch D is OFF)

The manual % dial allows the speed of the pump to be
manually adjusted and set by the user.  The speed of
the pump may be manually adjusted anywhere from
min to 100%, but once set remains fixed at that speed.
The “min” position on the dial will either be equal to
“OFF” or “15%” depending on the position of dip switch
C. The factory default is 50%.

Install control onto the pump. Insert the 115 V plug on
the line cord from the pump into a properly grounded
115 V outlet.  This will apply power to the pump/control.

Performance Indicator LEDs (Fig. 7)

Power ON (green) indicates power is applied.
% Out (Yellow) indicates the speed of the pump by
flashing at different rates.

Before You Leave

•   Place this brochure, and all other brochures
 

relating to the installation, in a conspicuous

 

location near the control for future reference.

•   It is important to explain the operation of this
 

control within the system to the end user and to

 

anyone else who may be operating the system.

Figure 7 - Performance

indicator LEDs

Multi Function Dial On Terminal Box

Offset Dial (When dip switch D is on)

The  Offset dial allows the user to fine tune the input
signal. The input signal may be varied plus or minus 1-
5%. This offset will affect the signal through it's entire
range.  The factory default is 0.  The offset setting
cannot increase the output to greater than 100% or less
than the selected minimum output of either 0% or 15%.

Example

:

The measured input signal is 2.1-10.1V and as a result
the pump does not shut off because the signal doesn't
drop to 2V. The dial is set to -5%
and the input signal is offset
down to 2.0-9.6V. The pump
will now shut off, however the
pump will not reach the full 10V
speed now, due to the offset.

Manual % Dial (When dip switch D is off)

The manual % dial allows the speed of the pump to be

manually adjusted and set by the user.  The speed of

the pump may be manually adjusted anywhere from

min to 100%, but once set remains fixed at that speed.

The "min" position on the dial will either be equal to

"OFF" or "15%" depending on the position of dip switch

C.  The factory default is 50%.

Performance Indicator LEDs (Fig. 7c)
Power ON

  (green)  indicates  power  is  applied.

% Out

(Yellow) indicates the speed of the pump by

flashing  at  different  rates.

Before You  Leave

Place this brochure, and all other brochures
relating to the installation, in a conspicuous
location near the control for future reference.

It is important to explain the operation of this
control within the system to the end user and to
anyone else who may be operating the system.

Page 8

Figure 7C -

  Performance

indicator LEDs

Figure 7B 

- % Offset

Offset /

Manual %

-5%

0

-1

-2

-3

-4

+1

+2

+3

+4

+5%

Min

100%

Summary of Contents for UP15-42F

Page 1: ...nd Operation 1 2 3 4 5 6 7 Electrical Pump Installation Operational Limits General Features Shipment Inspection Settings Quick Reference GRUNDFOS INSTRUCTIONS Pumps Incorporating the VS Variable Speed...

Page 2: ...roper installation and operation of this control could result in damage to the equipment and possibly even personal injury It is your responsibility to ensure that this control is safely installed acc...

Page 3: ...and safety devices must be added Offset dial provides fine tuning for input signal Manual dial provides manual speed control Range of signal is selected through Dip Switch A Type of signal used is se...

Page 4: ...re intended for use with water or a 50 50 mixture by weight of propylene glycol UP15 42F VS 115V 60 Hz Maximum Fluid Temperature 205 F 96 C Maximum Ambient 107 F 42 C with control module vertical Fig...

Page 5: ...freely Remove the large screw in the middle of the nameplate insert a small flat blade screwdriver into the end of the shaft and turn gently If the shaft does not turn easily repeat the disas sembly...

Page 6: ...ge remaining air from the bearing chamber This is especially important when installing the pump during the off season 5 Electrical Warning All electrical work should be performed by a qualified electr...

Page 7: ...he wires Current Speed Control Signal Connections Connect the current signal wires to terminals Com and Ret I Fig 3 Test the Speed Control Signal Wiring Make sure exposed wires and bare terminals are...

Page 8: ...f the pump will have a range from minimum speed 15 to a maximum speed 100 Dip Switch D speed control external speed control maximum dial When dip switch D is in the ON position an external V dc mA sig...

Page 9: ...al allows the speed of the pump to be manually adjusted and set by the user The speed of the pump may be manually adjusted anywhere from min to 100 but once set remains fixed at that speed The min pos...

Page 10: ...10V 4 20mA min speed off speedcontrol manual dial speedcontrol external A B C D 7 Quick Reference Setting Dip Switches Figure 7A DipSwitches Dip switch settings POSITION Feature Explanation Dip switc...

Page 11: ...s must be min 300V rating Sup Com Ret I Com Os V Boil Boil Dem Dem tN4 Fuse Transformer 1 VA 115 V 18 V 100 H 6 A inductor Pot 0 1 F 250V R Class 2 only Off On A B C D 1008 02 599395 May 2006 12345 Ma...

Page 12: ...te and sup porting installation data Unless otherwise provided the distributor or dealer will contact the GRUNDFOS factory or authorized service station for instructions Any defective product to be re...

Reviews: