Multi Function Dial On Terminal Box

Offset Dial (When dip switch D is on)

The  Offset dial allows the user to fine tune the input
signal. The input signal may be varied plus or minus 1-
5%. This offset will affect the signal through it's entire
range.  The factory default is 0.  The offset setting
cannot increase the output to greater than 100% or less
than the selected minimum output of either 0% or 15%.

Example

:

The measured input signal is 2.1-10.1V and as a result
the pump does not shut off because the signal doesn't
drop to 2V. The dial is set to -5%
and the input signal is offset
down to 2.0-9.6V. The pump
will now shut off, however the
pump will not reach the full 10V
speed now, due to the offset.

Manual % Dial (When dip switch D is off)

The manual % dial allows the speed of the pump to be
manually adjusted and set by the user.  The speed of

the  pump  may  be  manually  adjusted  anywhere  from
min to 100%, but once set remains fixed at that speed.
The "min" position on the dial will either be equal to

"OFF" or "15%" depending on the position of dip switch
C.  The factory default is 50%.

Install control onto the pump. Insert the 115 V plug on

the line cord from the pump into a properly grounded

115 V outlet. This will apply power to the pump/control.

Performance  Indicator  LEDs  (Fig.  7c)
Power  ON

  (green)  indicates  power  is  applied.

% Out

 

(Yellow) indicates the speed of the pump by

flashing  at  different  rates.

Before You  Leave

Place this brochure, and all other brochures
relating to the installation, in a conspicuous
location  near  the  control  for  future  reference.

It is important to explain the operation of this
control within the system to the end user and to
anyone else who may be operating the system.

Page 8

Page 3

 3.

Operational Limits

Control Signal Input Range

Voltage  signal  range:  0-10V(DC)  or  2-10V(DC)

Current  signal  range:  0-20mA  or  4-20mA

Grundfos Variable  Speed  pumps  are  designed  to  pump
liquids compatible with their cast iron pump housing
construction.  They are recommended for use in closed
hydronic  systems.  Grunfos Variable  Speed  pumps  are
for Indoor Use Only.

Grundfos Variable  Speed  Pumps  are  intended  for  use
with water, or a 50/50 mixture by weight of propylene
glycol.

UP15-42F/VS  115V  60  Hz Variable  Speed  Pump

Maximum  fluid  temperature:  205°F (96°C)

Maximum  ambient:

•  115°F (46°C) with control module vertical
    (Fig. 4a).
•  115°F (46°C) with control module under
    pump and horizontal (Fig. 4B).
•  105°F (40°C) with control module on top of
    pump and horizontal (Fig 4B).

Maximum  Working  Pressure:    145  PSI
Minimum  Inlet  Pressure:    5  PSI

UP26-96F/VS  115V  60HZ Variable  Speed  Pump
UP26-64F/VS  115V  60HZ  Variable  Speed  Pump

Maximum  fluid  temperature: 195°F (90°C)

Maximum  ambient:

•  105°F (40°C) with control module vertical
   (Fig. 4A).
•  105°F (40°C) with control module under
    pump and horizontal (Fig. 4B).
 •  92°F (33°C) with control module on top of
    pump and horizontal (Fig. 4B).

Maximum  Working  Pressure:    145  PSI
Minimum  Inlet  Pressure:    5  PSI

Figure 7C -

  Performance

indicator LEDs

Figure 7B 

- % Offset

Offset /

Manual %

-5%

0

-1

-2

-3

-4

+1

+2

+3

+4

+5%

Min

100%

Summary of Contents for UP15-42 Series

Page 1: ...was purchased together with proof of purchase and installation date failure date and supporting installation data Unless otherwise provided the distributor or dealer will contact the GRUNDFOS factory or authorized service station for instructions Any defective product to be returned to the factory or service station must be sent freight prepaid documentation supporting the warranty claim and or a ...

Page 2: ... result in damage to the equip ment and possibly even personal injury It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards This electronic control is not intended for use as a primary limit control Other controls that are intended and certified as safety limits must be placed into the control circuit Page 1 CONGRATULATIONS You ar...

Page 3: ... dip switch D Pump Exercising After every three days of no operation the control will exercise the pump for 10 seconds The Out LED will be on during exercising As variable speed output modulates the control flashes the out LED on for second and off for to 2 1 2 seconds The output is run at 100 for 3 seconds after power up reset for all modes of operation VoltageSpeedControl Signal Circuit Rating T...

Page 4: ...e You Leave Place this brochure and all other brochures relating to the installation in a conspicuous location near the control for future reference It is important to explain the operation of this control within the system to the end user and to anyone else who may be operating the system Page 8 Page 3 3 Operational Limits Control Signal Input Range Voltage signal range 0 10V DC or 2 10V DC Curre...

Page 5: ...ate direction of flow through the pump Grundfos Variable Speed pumps can be installed in both vertical and horizontal lines Figure 4A Prefered Terminal Box Orientation Figure 4B OptionalTerminal Box Orientation see Operational Limits Setting Dip Switches Figure 7A Dip Switches Dip switch settings POSITION Feature Explanation Dip switch C minimum speed off minimum speed 15 When dip switch C is in t...

Page 6: ...Provisions for a 115 V grounded outlet within 6 feet of the pump mounting location should be made Allelectricalworkshouldbeperformedbyaqualified electricianinaccordancewiththelatesteditionofthe NationalElectricalCode localcodesandregulations All speed control signal wiring terminates in the wiring chamber on the control All field installed wiring should meet or exceed requirements for class 2 wiri...

Page 7: ...ofthe NationalElectricalCode localcodesandregulations All speed control signal wiring terminates in the wiring chamber on the control All field installed wiring should meet or exceed requirements for class 2 wiring per article 725 of the National Electrical Code rated at 30VAC 250VA Test the Speed Control Signal Wiring Make sure exposed wires and bare terminals are not in contact with other wires ...

Page 8: ...indicate direction of flow through the pump Grundfos Variable Speed pumps can be installed in both vertical and horizontal lines Figure 4A Prefered Terminal Box Orientation Figure 4B OptionalTerminal Box Orientation see Operational Limits Setting Dip Switches Figure 7A DipSwitches Ý Dip switch settings POSITION Feature Explanation Dip switch C minimum speed off minimum speed 15 When dip switch C i...

Page 9: ...e You Leave Place this brochure and all other brochures relating to the installation in a conspicuous location near the control for future reference It is important to explain the operation of this control within the system to the end user and to anyone else who may be operating the system Page 8 Page 3 3 Operational Limits Control Signal Input Range Voltage signal range 0 10V DC or 2 10V DC Curre...

Page 10: ... dip switch D Pump Exercising After every three days of no operation the control will exercise the pump for 10 seconds The Out LED will be on during exercising As variable speed output modulates the control flashes the out LED on for second and off for to 2 1 2 seconds The output is run at 100 for 3 seconds after power up reset for all modes of operation VoltageSpeedControl Signal Circuit Rating T...

Page 11: ... result in damage to the equip ment and possibly even personal injury It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards This electronic control is not intended for use as a primary limit control Other controls that are intended and certified as safety limits must be placed into the control circuit Page 1 CONGRATULATIONS You ar...

Page 12: ...was purchased together with proof of purchase and installation date failure date and supporting installation data Unless otherwise provided the distributor or dealer will contact the GRUNDFOS factory or authorized service station for instructions Any defective product to be returned to the factory or service station must be sent freight prepaid documentation supporting the warranty claim and or a ...

Reviews: