English (GB)
50
Advanced control panel and wireless pump connection
1. Power on both pumps.
2. On both pumps, set the needed analog and digital inputs
according to the connected equipment and the required
functionality. See section
.
3. Select the "Assist" menu on one of the pumps and choose
"Setup of multi-pump system".
4. Press [>] to continue.
5. Select "Wireless" as the communication method to be used
between the two pumps.
6. Press [>] to continue.
7. Select the desired multipump function. See section
and
above.
8. Press [>] three times to continue.
9. Press [OK] to search for other pumps.
The green indicator light in the middle of Grundfos Eye will
flash on the other pumps.
10. Press the connect button on the pump which is to be added to
the multipump system.
11. Press [>] to continue.
12. Set the time for pump changeover i.e. the time at which the
alternation between the two pumps is to take place.
13. Press [>] to continue.
14. Press [OK].
The multipump function icons appear in the bottom of the
control panels.
The multipump system has now been set.
Advanced control panel and wired pump connection
1. Connect the two pumps with each other with a 3-core
screened cable between the GENIbus terminals A, Y, B.
2. Set the needed analog and digital inputs according to the
connected equipment and the required functionality. See
section
.
3. Assign pump number 1 to the first pump. See section
.
4. Assign pump number 2 to the other pump. See section
.
5. Select the "Assist" menu on one of the pumps and choose
"Setup of multi-pump system".
6. Press [>] to continue.
7. Select "Wired GENIbus" as the communication method to be
used between the two pumps.
8. Press [>] twice to continue.
9. Select the desired multipump function. See section
10. Press [>] to continue.
11. Press [OK] to search for other pumps.
12. Select the additional pump from the list.
13. Press [>] to continue.
14. Set the time for pump changeover i.e. the time at which the
alternation between the two pumps is to take place.
15. Press [>] to continue.
16. Press [OK].
The multipump function icons will appear in the bottom of the
control panels.
The multipump system has now been setup.
Disabling the multipump function via Grundfos GO
1. Select the "Assist" menu.
2. Select "Multipump setup".
3. Select "Disable".
4. Press [>] to continue.
5. Confirm the multipump setup by pressing [Send].
6. Press [Finish].
The multipump function has now been disabled.
Disabling a multipump via advanced control panel
1. Select the "Assist" menu.
2. Select "Setup of multi-pump system".
3. Press [>] to continue.
4. Confirm No multi-pump function by pressing [OK].
5. Press [>] to continue.
6. Press [OK].
The multipump system has now been disabled.
14.48 Description of control mode
This menu is only available in the advanced control panel.
This menu describes each of the possible control modes. See
also section
14.49 Assisted fault advice
This menu gives guidance and corrective actions in case of pump
failures.
Note
This step applies only if you have selected
"Alternating operation, time" and if the pumps are
fitted with FM 300.
Note
This step applies only if you have selected
"Alternating operation, time" and if the pumps are
fitted with FM 300.