12
English (US)
Alarm output signal
An alarm output signal is available.
Output transistor status indicates pump operation.
Output signal is activated if:
•
Stop (input signal 0.5 V - 2 V)
•
Stop (because of an alarm) (input signal 2 V - 10 V)
Output signal is not activated if:
•
Pump fault.
•
Running (input voltage < 0.5 V) (interpreted as cable break).
Rating
Value
Rated input voltage - high level
U
IH
4-24 V
Rated input voltage - low level
U
IL
< 1 V
High-level input current
I
IH
< 10 mA
PWM frequency output, open collector
f
75 Hz ± 5 %
Accuracy of output signal regarding power consumption
-
± 2 % of PWM signal
Collector-emitter breakdown voltage on output transistor
U
C
< 70 V
Collector current on output transistor
I
C
< 50 mA
Max. power dissipation on output resistor
P
R
125 mW
Zener diode working voltage
U
Z
36 V
Max. power dissipation in Zener diode
P
Z
300 mW