4.4.1 Starting method
Continuous operation
We recommend star-delta starting, soft starter or
frequency converter throughout the entire power
range.
Intermittent operation
Start via softstarter or frequency converter is
mandatory throughout the entire power range.
4.4.2 Wiring diagrams
Fig. 11
Three thermal switches (PTO)
Fig. 12
Three PTC sensors
4.4.3 Direction of rotation
When the electrical connections have been carried
out, check that the impeller is rotating in the correct
direction. When viewed from the motor, the impeller
must rotate clockwise. An arrow on the motor
housing shows the correct direction of rotation.
If the impeller rotates in the wrong direction,
interchange two phases of the mains supply (L1, L2,
L3).