background image

12

8. Fault finding chart

Fault Cause 

Remedy

1. The pump does not run. 

a) The fuses are blown. 

Replace the blown fuses. If the new ones blow too,
the electric installation and the submersible drop cable 
should be checked. 

b) The ELCB or the voltage-operated ELCB 

has tripped out. 

Cut in the circuit breaker. 

c) No electricity supply. 

Contact the electricity supply authorities. 

d) The motor starter overload has tripped out. 

Reset the motor starter overload (automatically or
possibly manually). If it trips out again, check the
voltage. Is the voltage OK, see items e) - h). 

e) Motor starter/contactor is defective. 

Replace the motor starter/contactor. 

f)

Starter device is defective. 

Repair/replace the starter device. 

g) The control circuit has been interrupted or is 

defective. 

Check the electric installation. 

h) The dry-running protection has cut off the 

the electricity supply to the pump, due to low 
water level. 

Check the water level. If it is OK, check the water level 
electrodes/level switch. 

i)

The pump/submersible drop cable is defec-
tive. 

Repair/replace the pump/cable.

2. The pump runs but

gives no water. 

a) The discharge valve is closed. 

Open the valve. 

b) No water or too low water level in borehole. 

See item 3 a).

c) The non-return valve is stuck in its shut posi-

tion. 

Pull out the pump and clean or replace the valve. 

d) The inlet strainer is choked up. 

Pull out the pump and clean the strainer. 

e) The pump is defective. 

Repair/replace the pump.

3. The pump runs at

reduced capacity. 

a) The drawdown is larger than anticipated. 

Increase the installation depth of the pump, throttle
the pump or replace it by a smaller model to obtain a 
smaller capacity. 

b) Wrong direction of rotation. 

See section 4.5.1 Checking of direction of rotation

c) The valves in the discharge pipe are partly 

closed/blocked.

Check and clean/replace the valves, if necessary. 

d) The discharge pipe is partly choked by

impurities (ochre). 

Clean/replace the discharge pipe. 

e) The non-return valve of the pump is partly 

blocked. 

Pull out the pump and check/replace the valve. 

f)

The pump and the riser pipe are partly 
choked by impurities (ochre). 

Pull out the pump. Check and clean or replace the 
pump, if necessary. Clean the pipes. 

g) The pump is defective. 

Repair/replace the pump. 

h) Leakage in the pipework. 

Check and repair the pipework.

i)

The riser pipe is defective. 

Replace the riser pipe.

4. Frequent starts and 

stops. 

a) The differential of the pressure switch

between the start and stop pressures is too 
small. 

Increase the differential. However, the stop pressure 
must not exceed the operating pressure of the pres-
sure tank, and the start pressure should be high 
enough to ensure sufficient water supply. 

b) The water level electrodes or level switches 

in the reservoir have not been installed
correctly. 

Adjust the intervals of the electrodes/level switches to 
ensure suitable time between the cutting-in and
cutting-out of the pump. See Installation and Operating 
Instructions for the automatic devices used. If the
intervals between stop/start cannot be changed via the 
automatics, the pump capacity may be reduced by 
throttling the discharge valve. 

c) The non-return valve is leaking or stuck

half-open. 

Pull out the pump and clean/replace the non-return 
valve. 

d) The volume of air in the pressure/diaphragm 

tank is too small. 

Adjust the volume of air in the pressure/diaphragm 
tank in accordance with its Installation and Operating 
Instructions. 

e) The pressure/diaphragm tank is too small. 

Increase the capacity of the pressure/diaphragm tank 
by replacing or supplementing with another tank. 

f)

The diaphragm of the diaphragm tank is
defective.

Check the diaphragm tank.

Summary of Contents for SP-G

Page 1: ...SP G GRUNDFOS INSTRUCTIONS Installation and operating instructions ...

Page 2: ... 60335 1 2002 e EN 60335 2 41 2003 excepto nos pontos 25 1 e 25 8 Bomba com ponta de veio livre A Grundfos declara sob sua única responsabilidade que os produtos SP G aos quais diz respeito esta declaração estão em conformidade com as seguintes Directivas do Conselho sobre a aproximação das legislações dos Estados Membros da CE Directiva Máquinas 2006 42 CE Norma utilizada EN 809 2009 Antes de col...

Page 3: ...24 Istruzioni di installazione e funzionamento 34 Instrucciones de instalación y funcionamiento 43 Instruções de instalação e funcionamento 52 Οδηγίες εγκατάστασης και λειτουργίας 62 Installatie en bedieningsinstructies 72 Monterings och driftsinstruktion 82 Asennus ja käyttöohjeet 91 Monterings og driftsinstruktion 100 ...

Page 4: ...e a month If a motor has been stored for more than one year before installa tion the rotating parts of the motor must be dismantled and checked before use The pump should not be exposed to direct sunlight If the pump has been unpacked it should be stored horizontally adequately supported or vertically to prevent misalignment of the pump Make sure that the pump cannot roll or fall over During stora...

Page 5: ...ith the filling syringe fig 3 until the liquid runs back out of the filling hole 4 Replace the screw in the filling hole and tighten securely before changing the position of the pump Torque 3 0 Nm The submersible pump is now ready for installation Fig 3 3 1 3 Refilling GRUNDFOS submersible motors MMS 6000 MMS 8000 MMS 10000 and MMS 12000 To refill the motor proceed as follows 1 Position the submer...

Page 6: ...tor makes See motor specifications 4 Electrical connection 4 1 General The electrical connection should be carried out by an authorized electrician in accordance with local regulations The supply voltage rated maximum current and cos appear from the loose data plate that must be fitted close to the installa tion site The required voltage quality for GRUNDFOS MS submersible motors measured at the m...

Page 7: ...ter must be protected by means of a motor starter with thermal relay or a CU 3 and contactor s GRUNDFOS MMS motors have no built in temperature transmit ter A Pt100 sensor is available as an accessory Motors with a Pt100 sensor must be protected by means of a motor starter with thermal relay or a CU 3 and contactor s Motors without a Pt100 sensor must be protected by means of a motor starter with ...

Page 8: ... Specific resistance 0 02 mm m q Cross section of submersible drop cable mm sin 0 436 Xl Inductive resistance 0 078 x 10 3 m 4 5 Connection of motor Three phase submersible motors must be protected see section 4 2 Motor protection For electrical connection by means of the CU 3 see the separate installation and operating instructions for this unit When a conventional motor starter is being used the...

Page 9: ...ightened diagonally to the torques stated in the following table Note Make sure that the pump chambers are aligned when assembly has been completed 5 2 Fitting of submersible drop cable Before fitting the submersible drop cable to the motor make sure that the cable socket is clean and dry To facilitate the fitting of the cable lubricate the rubber parts of the cable plug with non conducting silico...

Page 10: ...osed off to approx 1 3 of its maximum volume of water Check the direction of rotation as described in section 4 5 1 Checking of direction of rotation If there are impurities in the water the valve should be opened gradually as the water becomes clearer The pump should not be stopped until the water is completely clean as otherwise the pump parts and the non return valve may choke up As the valve i...

Page 11: ...d at a GRUNDFOS service centre If GRUNDFOS is requested to service the pump GRUNDFOS must be contacted with details about the pumped liquid etc before the pump is returned for service Otherwise GRUNDFOS can refuse to accept the pump for service Possible costs of returning the pump are paid by the customer If a pump has been used for a liquid which is injurious to health or toxic the pump will be c...

Page 12: ... rotation c The valves in the discharge pipe are partly closed blocked Check and clean replace the valves if necessary d The discharge pipe is partly choked by impurities ochre Clean replace the discharge pipe e The non return valve of the pump is partly blocked Pull out the pump and check replace the valve f The pump and the riser pipe are partly choked by impurities ochre Pull out the pump Check...

Page 13: ... the full load current there are the following possible faults The contacts of the motor starter burnt Replace the con tacts Poor connection in leads possibly in the cable joint See item 3 Too high or too low supply voltage See item 1 The motor windings are short circuited or partly disjointed See item 3 Damaged pump is causing the motor to be overloaded Pull out the pump for overhaul The resistan...

Page 14: ... Bride Flangia Brida Flange Φλάντζα Flens Fläns Laippa Flange Motor Motor Moteur Motore Motor Motor Κινητήρας Motor Motor Moottori Motor Direct On Line Starting Direktanlauf Démarrage direct Avviamento diretto Arranque directo Arranque directo Απευθείας Εκκίνηση Directe aanloop Direktstart Suorakäynnistys Direkte start Star Delta Starting Stern Dreieck Anlauf Démarrage étoile triangle Avviamento Y...

Page 15: ... 3 x 400 V I 40 A L 140 m U 2 Lx L U 140 2 70 m q 25 mm 2 TM00 1346 5092 I 40 A U 2 U 3 x 400 V L 140 m Example U 3 x 380 V I 10 A L 120 m U 2 Lx L U 120 2 60 m q 6 mm 2 TM00 1345 5092 I 10 A U 2 U 3 x 380 V L 120 m ...

Page 16: ...3 x 220 V I 5 A L 105 m U 3 Lx L U 105 3 35 m q 2 5 mm 2 TM00 1348 5092 I 5 A U 3 U 3 x 220 V L 105 m Example U 3 x 415 V I 100 A L 150 m U 3 Lx L U 150 3 50 m q 50 mm 2 TM00 1347 5092 I 100 A U 3 U 3 x 415 V L 150 m ...

Page 17: ...112 ...

Page 18: ...113 ...

Page 19: ...114 ...

Page 20: ...ps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn Bhd 7 ...

Page 21: ...www grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96432078 0711 Repl 96432078 0506 ECM 1078259 ...

Reviews: