7.2 Start/stop according to water 

consumption 

As default, the PM Rain is set to this operating 
mode, i.e. DIP switch 5 set to "OFF".

7.2.1 Starting and stopping conditions

Starting conditions

The unit starts the pump when at least one of the 
following conditions is fulfilled:

The flow is higher than Q

min.

.

The pressure is lower than p

start

.

The default start pressure is 2.5 bar (250 kPa) 
and can be increased in steps of 0.5 bar (50 kPa). 
See section 5.1 DIP switches.

Stopping conditions

The unit stops the pump with a time delay of 
10 seconds when the following conditions are both 
fulfilled:

The flow is lower than Q

min.

: 1.0 l/h.

The pressure is higher than p

start

2.5 bar (250 kPa) (factory setting). 
See section 11. Technical data.

7.3 Start/stop with 1 bar (100 kPa) 

differential pressure 

This operating mode can be used in systems with 
a pressure tank of a sufficient size. 

In this operating mode, the pump is started and 
stopped at a 1 bar (100 kPa) differential pressure, 
which reduces the pump operating time. If the 
pressure tank is of an insufficient size, it will cause 
cycling of the pump.

To enable this operating mode, set DIP switch 5 to 
"ON". See section 5.1 DIP switches.

7.3.1 Starting and stopping conditions

The conditions described below require that DIP 
switch 5 has been set to "ON".

Starting conditions

The unit starts the pump when the pressure is lower 
than p

start

.

The default start pressure is 2.5 bar (250 kPa) and 
can be increased in steps of 0.5 bar (50 kPa). 
See section 5.1 DIP switches.

Stopping conditions

The unit stops the pump when the pressure is higher 
than p

stop

p

stop

 = p

start

 + 1 bar (100 kPa).

7.3.2 Setting the precharge pressure of the 

pressure tank

The precharge pressure should be 0.14 bar (14 kPa) 
below the pump start pressure. 

8. Functions 

When the auto-reset function is enabled, cycling and 
dry-running warnings will be automatically reset.

To enable the function, set DIP switch 6 to "ON". 
See section 5.1 DIP switches.

8.1 Anti-cycling

To detect inadvertent starts and stops of the pump in 
case of a failure in the installation, the anti-cycling 
function can be enabled.

The function will detect cycling if it occurs and the 
red "Warning" indicator light will illuminate.

When the PM Rain has been set to start/stop 
according to water consumption, cycling may occur 
in the following situations:

In case of a minor leakage.

If a tap has not been entirely closed.

When the PM Rain has been set to start/stop with 
1 bar (100 kPa) differential pressure, cycling may 
occur in the following situations:

If the pressure tank has lost its precharge 
pressure.

If the size of the pressure tank is insufficient. 

If the cycling warning has been activated, the pump 
can be restarted manually by pressing [Reset].

When the auto-reset function is enabled, the pump 
will be restarted automatically after 12 hours in 
warning condition.

To enable the function, set DIP switch 7 to "ON". 
See section 5.1 DIP switches.

8.2 Dry-running protection

The PM Rain incorporates dry-running protection 
that automatically stops the pump in case of dry 
running.
The dry-running protection functions differently 
during priming and operation. 

8.2.1 Dry running during priming 

If the unit detects no pressure and no flow within 
3 minutes after it has been connected to a power 
supply and the pump has started, the dry-running 
warning is activated.

8.2.2 Dry running during operation

If the unit detects no pressure and no flow within 
40 seconds during normal operation, the dry-running 
warning is activated.

Caution

With the default setting the pump will 
not stop until it reaches its maximum 
pressure.

Note

In case of a very small consumption, 
the anti-cycling function may register 
this as a minor leakage and stop the 
pump inadvertently. If this occurs, the 
function can be disabled.

Caution

If a dry-running warning has been 
activated, the cause should be found 
before the pump is restarted in order to 
prevent damage to the pump.

Summary of Contents for PM Rain

Page 1: ...GRUNDFOS INSTRUCTIONS PM Rain Installation and operating instructions...

Page 2: ...proximation of the laws of the EC member states Low Voltage Directive 2006 95 EC Standards used EN 60730 1 2000 and EN 60730 2 6 2008 EMC Directive 2004 108 EC Standards used EN 60730 1 2000 and EN 60...

Page 3: ...Functions 10 8 1 Anti cycling 10 8 2 Dry running protection 10 9 Frost protection 11 10 List of warnings 12 11 Technical data 12 12 Fault finding 13 13 Further product information 14 14 Disposal 14 W...

Page 4: ...hout solid particles or fibres that may attack the unit mechanically or chemically 3 2 Temperatures 3 2 1 Liquid temperature 0 to 60 C 3 2 2 Ambient temperature 0 to 55 C 3 3 Operating pressure Max 10...

Page 5: ...e unit so that the height between the unit and the highest tapping point does not exceed the values in the table below Default setting See section 5 1 DIP switches Note Use a suitable thread seal tape...

Page 6: ...rther adjustment is necessary repeat from point 2 When the pressure reducing valve has been adjusted correctly adjust the start pressure accordingly See section 5 1 DIP switches 10 Refit the PM Rain c...

Page 7: ...l installation make sure that the power supply cannot be accidentally switched on The unit must be connected to an external mains switch with a minimum contact gap of 3 mm in all poles As a precaution...

Page 8: ...witch 2 ON Start pressure 2 5 0 5 1 4 bar Start pressure 250 50 100 400 kPa See section 7 2 1 Starting and stopping conditions All set to OFF pstart 2 5 bar pstart 250 kPa 5 STOP START 1 BAR Start sto...

Page 9: ...at a pressure above 2 5 bar 250 kPa the mains water back up will remain inactive See fig 7 If rainwater is no longer available the PM Rain will stop the pump when dry running occurs When the system p...

Page 10: ...atically reset To enable the function set DIP switch 6 to ON See section 5 1 DIP switches 8 1 Anti cycling To detect inadvertent starts and stops of the pump in case of a failure in the installation t...

Page 11: ...not been primed within 3 minutes of operation the dry running warning will reappear The auto reset function will attempt to restart the pump after 24 hours This will be repeated for five days and if r...

Page 12: ...art stop sequences within a short period Each pump start is delayed a few seconds to protect the installation The start delay is active until normal operation has been re established Note The protecti...

Page 13: ...ump is blocked c The pump is defective Repair or replace the pump d The PM Rain is defective Repair or replace the PM Rain 3 The pump does not start when water is consumed Pump on is off a Too big dif...

Page 14: ...ction 8 1 Anti cycling b Cycling There is a minor leakage in the system Note For system without pressure tank Check the system for leaks See section 8 1 Anti cycling c Cycling The pressure tank has no...

Page 15: ...ndix 1 Fig 8 Wiring diagrams Fig 9 Dimensions TM04 9528 4510 TM04 1953 1508 IN M 3 L1 L3 N L1 L2 PE N U V 1x230 V 50 60 Hz PE 6 OUT 5 4 3 2 1 IN M 1 L1 L1 N PE N U V 1x230 V 50 60 Hz PE 6 OUT 5 4 3 2...

Page 16: ...16...

Page 17: ...17...

Page 18: ...18...

Page 19: ...Peguam U1 25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone 60 3 5569 2922 Telefax 60 3 5569 2866 New Zealand GRUNDFOS Pumps NZ Ltd 17 Beatrice Tinsley Crescent North Harbour Industrial Est...

Page 20: ...ahead makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denma...

Reviews: