5.9.3 Displaying the current input value for the water flow
meter
1. MAIN MENU > SERVICE > [OK].
2. WATER FLOW METER > [OK].
Displaying the current input value for the contact water
meter
•
"Pulses per second", which correspond to the pulse rate
(xxx litres per pulse), and the flow.
•
Disturbance variable in percent.
-------------------------------------------------------------------------------------
Calculation example with 5 l/pulse, Q
max.
= 2000 l/h:
2 m
3
= 2000 l;
2000/5 = 400 pulses/h = 0.11 pulses/sec.
This corresponds to a disturbance variable of 100 %.
-------------------------------------------------------------------------------------
In case the defined input values are exceeded or not reached, a
fault has occurred, for example at the water flow meter.
Displaying the current input value for the flow meter
•
Corresponding current for the flow (in mA).
•
Disturbance variable (in percent).
5.9.4 Displaying the process status
Examples:
1. MAIN MENU > SERVICE > [OK].
2. PROCESS > [OK].
3. STATUS > [OK].
5.9.5 Displaying the list of events
1. MAIN MENU > SERVICE > PROCESS > [OK].
2. LIST OF EVENTS > [OK].
5.9.6 Displaying the number of ClO
2
cycles
1. MAIN MENU > SERVICE > [OK].
2. ClO
2
PRODUCTION > [OK].
3. CYCLES > [OK].
After 9999 cycles, the display is reset to 0.
5.9.7 Displaying the maintenance date
1. MAIN MENU > SERVICE > [OK].
2. ClO
2
PRODUCTION > [OK].
3. MAINTENANCE > [OK].
5.9.8 Displaying or resetting the chemical consumption after
changing containers
The control system calculates the chemical consumption and
displays this in litres. It starts automatically at 0.000 l.
Displaying the chemical consumption
1. MAIN MENU > SERVICE > [OK].
2. PROCESS > [OK].
3. ClO
2
PRODUCTION > [OK].
4. CHEMICALS > [OK].
5. HCl > [OK].
6. Press [Esc].
7. NaClO
2
> [OK].
See the example for HCl.
8. Press [Esc].
Resetting the chemical consumption
1. ClO
2
PRODUCTION > [OK].
2. CHEMICALS > [OK].
3. RESET > [OK].
4. HCl > [OK].
The consumption meter is reset to 0.
5. NaClO
2
> [OK].
The consumption meter is reset to 0.
WATER FLOW METER
0.00 pulses/sec.
0 %
WATER FLOW METER
0 mA
0 %
PROCESS STATUS
HCl SUPPLY RUNNING
LIST OF EVENTS
NUMBER...................... 1/99
PROCESS ABORTION
2008-07-22 . . . . . . . . . 11:45
ClO2 PRODUCTION
25
CYCLES
MAINTENANCE
LAST
2008-07-25
NEXT
2008-09-25
CHEMICALS
HCl
NaClO
2
RESET
HCl
0.000 L
Since 2008-07-31
RESET
HCl
NaClO
2