11. Fault finding

Warning
Before carrying out any work on lifting stations used 
for pumping liquids which might be hazardous to 
health, make sure that the lifting station has been 
thoroughly flushed with clean water and that the 
outlet pipe has been drained. Rinse the parts in 
water after dismantling. Make sure that the isolating 
valves have been closed. 
The work must be carried out in accordance with 
local regulations.
Before making any connections in the LC 221 or 
work on lifting stations, etc., it must be ensured that 
the power supply has been switched off and that it 
cannot be accidentally switched on.

Fault

Cause

Remedy

1. The pump(s) does/do 

not run.

a) No power supply.

None of the indicator lights are on.

With battery backup: 

See section 

5.2 LC 221 controller

.

Switch on the power supply or wait until the power cut is 
over. During the power cut, drain the collecting tank with 
diaphragm pump.

b) The ON-OFF-AUTO selector switch is in 

position OFF ( ), see section 

6. Operating 

LC 221 controller

.

Push the ON-OFF-AUTO selector switch into position 
ON ( ) or AUTO ( ).

c) Control circuit fuses are blown.

Check and eliminate the cause. Replace the control 
circuit fuses.

d) The motor-protective circuit breaker has cut 

out the pump (only relevant if a 
motor-protective circuit breaker has been 
installed). The pump symbol in the display is 
flashing and the red indicator light for fault is 
flashing. The fault indication in the display is 
RELAY and the fault code is F018.

Check the pump and tank as well as the setting of the 
motor-protective circuit breaker. If the pump is blocked, 
remove the blockage. If the setting of the 
motor-protective circuit breaker is wrong, readjust it 
(compare the setting with the nameplate).

e) Motor/supply cable is defective or the 

connections have become loose.

Check motor and supply cable. Replace cable or 
retighten connections if necessary.

f)

The fault indication in the display is 
SENSOR and in the fault code is F005 
and/or F006.

Clean the level sensor (see section 

10.3 Cleaning the 

level sensor

), and start up again. Check the cable and 

the connection on the controller board. If the signal is 
still wrong, please call Grundfos service.

g) The module power circuit board or the LCD 

board is defective.

Replace the PCB or LCD board.

2. The sensor signal is out 

of range. 
All pumps are started 
and high level alarm is 
on.

a) Not all outlet valves are open.

Open all outlet isolating valves.

b) There is a blockage in the tank or pump.

Remove the blockage.

c) The pump is not vented correctly. The pump 

cannot build up pressure.

1. Check that the vent hose is correctly fitted between 

the vent flange and the tank.

2. Remove any blockage from the vent hole at the 

outlet port.

d) The lifting station is undersized.

Recalculate the inflow parameters and compare the 
result with the tank volume and pump performance. If 
you need a new product, contact the nearest Grundfos 
sales company.

Summary of Contents for Multilift MDG

Page 1: ...Multilift MOG MDG Installation and operating instructions GRUNDFOS INSTRUCTIONS Other languages http net grundfos com qr i 98127057...

Page 2: ...221 controller 11 6 1 Description of display 11 6 2 Setup menu 13 6 3 Information menu 14 6 4 Description of fault indications 15 7 Installation of lifting station 17 7 1 General description 17 7 2 Gu...

Page 3: ...er system and vortex impeller 2 Lifting bracket 3 Nameplate 4 Venting port DN 70 outer diameter 75 mm open 5 Screw cap for pressure tube and tank inspection opening 6 Vertical inlet DN 150 seal is acc...

Page 4: ...hazardous substances such as greasy wastewater from large scale catering establishments For drainage of greasy wastewater use a grease separator according to EN 1825 2 between a canteen or commercial...

Page 5: ...net Three phase motors are protected by a thermal switch in the windings and an additional thermal circuit breaker in the cabinet to cut out the motor in case of overload If the phase sequence for thr...

Page 6: ...The control box uses the analogue signal to start and stop the pump and to indicate high water level alarm The pressure tube is fixed underneath the screw cap and can be taken out for maintenance ser...

Page 7: ...nnection of thermal switches and a runtime limitation motor protection via operation time limitation with subsequent emergency operation Normal operating times are max 90 seconds with pipework DN 32 a...

Page 8: ...mmon alarm output which is a potential free changeover contact can be used to forward the alarm signal to a control room by means of an external power source Type key LC 221 controller Nameplate LC 22...

Page 9: ...are described in section 6 1 Description of display Operating buttons pos 2 The level controller is operated by the operating buttons placed under the display The function of the operating buttons is...

Page 10: ...Potential free changeover contacts NO NC with max 250 V 2 A Attention Connect these terminals to supply network potential or low voltage but do not mix the two X11 9 Terminals for high water level ala...

Page 11: ...ible if the level controller detects a fault and the fault will be written into the fault log After you have entered the fault log the symbol will switch off See section 6 3 Information menu Setup The...

Page 12: ...fault in pump 1 The symbol is visible when pump 1 is running and flashes when pump 1 has a fault In case of fault it can be combined with other symbols or fault codes in the display Pump operation an...

Page 13: ...sing the button Enter values or select settings from a list by means of the buttons and Save the settings by pressing the button See also fig 15 The following settings can be made start level rated cu...

Page 14: ...enu by means of the buttons and Select the desired menu item by pressing the button See also fig 16 In the information menu the following data can be read fault indications operating hours number of s...

Page 15: ...g time and the controller has stopped the pump for a defined 2cool down period in order to prevent overheating The operating time and cool down period depend on the pump See the duty type on the namep...

Page 16: ...g is open If automatic resetting was selected in menu setup the red LED and the symbol will disappear and the buzzer will be deactivated again after the fault has disappeared has been removed or the O...

Page 17: ...observed 7 1 1 Installation sketch Fig 18 Installation sketch TM05 2143 4511 4 6 2 1 5 3 Pos Accessories Product number 1 Socket seal DN 100 97726942 2 Socket seal DN 50 98079669 3 Diaphragm pump 1 1...

Page 18: ...ation for black wastewater must be vented above roof level However it is permitted to lead the ventilation as a secondary ventilation into the main building ventilation system Special vent valves acce...

Page 19: ...Optional DN 150 inlet disk adjustable from 207 to 279 mm above the floor to the middle of the inlet pipe Fig 21 Untightened screw in outer ring Fig 22 Plugging the main inlet 3 Prepare optional inlets...

Page 20: ...be ensured if a distance of approx 3 cm is left between the vent pipe end and the vent port 8 Connect the diaphragm pump optional Fit the diaphragm pump on the outlet side To facilitate servicing of...

Page 21: ...ugh the cable entries and gaskets The power outlet must be placed near the cabinet as the controller is supplied with a 1 5 m cable Maximum backup fuse is stated on the controller nameplate Warning Wh...

Page 22: ...of a swimming pool is connected to Multilift MOG or MDG The preset value is 5 seconds Maintenance interval The maintenance service interval can be set to 0 3 6 or 12 months and is indicated in the SER...

Page 23: ...peration Replace defective ball bearings A general overhaul of the pump is usually required in case of defective ball bearings or poor motor function This work must be carried out by the manufacturer...

Page 24: ...G or MDG Fig 30 Removing the level sensor 10 4 Contaminated lifting station or components If Grundfos is requested to service the lifting station Grundfos must be contacted with details about the pump...

Page 25: ...and the red indicator light for fault is flashing The fault indication in the display is RELAY and the fault code is F018 Check the pump and tank as well as the setting of the motor protective circuit...

Page 26: ...ocked clean the vent hole c The thermal switch has cut out the pump The pump and thermal switch symbols on the display are flashing and the red indicator light for fault is permanently on The fault in...

Page 27: ...iron Impeller PPE PS Pump shaft Stainless steel DIN W Nr 1 4301 Motor cable Polychloroprene O rings NBR rubber Controller Voltage variants rated voltages 1 x 230 V 3 x 230 V 3 x 400 V Voltage toleran...

Page 28: ...I MOG 12 3 2 3 x 400 V 3 1 21 2750 CEE 3P N E 16 A MOG 15 3 2 3 x 230 V 2 3 1 5 6 6 36 2700 2 CEE 3P E 16 A MOG 15 3 2 3 x 400 V 3 8 21 2700 CEE 3P N E 16 A MOG 26 3 2 3 x 230 V 3 7 2 6 9 2 57 2870 2...

Page 29: ...Appendix 29 Appendix 1 Fig A Dimensional sketch MOG TM05 0672 1011...

Page 30: ...Appendix 30 Fig B Dimensional sketch MDG TM05 0443 1011...

Page 31: ...53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava b...

Page 32: ...splayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2018 Grundfos Holding A...

Reviews: