8. Operating the product
8.1 Setting the controller
8.1.1 Setting the start level
When you switch on the controller for the first time, the startup wizard guides you through the nec-
essary settings. If you later want to change the start level, follow these steps:
1. Go to the settings menu.
2. Press
OK
.
3. Go to menu
L_01
.
4. Press
OK
.
5. Select the start level.
•
Select 450 mm if the low inlet is used.
•
Select 700 mm if the high inlet is used.
Select 450 mm if the inlet pipe height is between the two values.
6. Press
OK
.
8.1.2 Setting the rated current
When you switch on the controller for the first time, the startup wizard guides you through the nec-
essary settings. If you later want to change the rated motor current, follow these steps:
1. Go to the settings menu.
2. Press
OK
.
3. Go to menu
I_02
.
4. Press
OK
.
5. Press arrow right or left to set the rated current according to the motor nameplate.
6. Press
OK
.
8.1.3 Setting the stop delay
1. Go to the settings menu.
2. Press
OK
.
3. Go to menu
T_01
.
4. Press
OK
.
5. Press arrow right or left to set the delay in seconds.
6. Press
OK
.
8.1.4 Setting the start delay
1. Go to the settings menu.
2. Press
OK
.
3. Go to menu
T_02
.
4. Press
OK
.
5. Press arrow right or left to set the delay in seconds.
The factory setting is 0.
6. Press
OK
.
8.1.5 Setting the alarm delay
1. Go to the settings menu.
2. Press
OK
.
3. Go to menu
T_03
.
4. Press
OK
.
5. Press arrow right or left to set the delay in seconds.
6. Press
OK
.