9
4. Systems with 3 levels (4 electrodes)
Description (see also page 98):
The pump is controlled by the liquid level in the pit.
•
The electrode, pos. 2, starts the pump.
•
The electrode, pos. 1, stops the pump. It is possible to set a
“stop delay” which delays the stop of the pump.
•
The top electrode, pos. 3, activates the high-level alarm.
4.1 Electrical connection
Systems with 3 levels (4 electrodes), page 98.
Figure B1 on page 98 shows all electrical connections required to
connect the LC 110 for
3 levels (4 electrodes)
.
The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the elec-
tricity supply on which it will be used.
All cables/wires must be fitted through the Pg cable entries and
gaskets (IP 65).
Maximum back-up fuse is stated on the controller nameplate.
If required according to local regulations, an external mains
switch must be installed.
Note:
If the motor PTC resistor/thermal switch is connected, the
factory-fitted short-circuit jumper
must be removed
(terminals
T11-T21). For correct installation of PTC resistor/thermal switch,
see the installation and operating instructions of the pump.
Key to the symbols in fig. B1 on page 98:
4.2 Setting
Systems with 3 levels (4 electrodes), page 98.
The module CU 213 has a 10-pole DIP switch in the bottom right
corner, see fig. 5.
Note:
During setting, the controller must be off circuit for at least
1 minute to ensure the correct configuration during start-up after
change of the DIP switch setting.
The DIP switch setting offers the following possibilities:
•
selection of starting delay and automatic test run (switch 4),
•
setting of stop delay (switches 5, 6 and 7),
•
selection of automatic alarm resetting (switch 9),
•
selection of automatic restarting (switch 10).
Fig. 5
Set the DIP switch as shown in fig. 5.
Each individual switch (1 to 10) of the DIP switch can be set to
position OFF or ON.
Note:
The DIP switch
must
not
be set to other switch combina-
tions than those described in this section.
Set the switches 1 to 10 as follows:
•
Switches
1
,
2
and
3
, application type:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
•
Switch
4
, starting delay and automatic test run
(only in the case of battery back-up):
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
Before starting any work on pumps used to pump liq-
uids which could be constituted as being hazardous
to health, thorough cleaning/venting of pumps, pits,
etc. must be carried out according to local regula-
tions.
Before making any connections in the LC 110 or work
on pumps, pits, etc., it must be ensured that the elec-
tricity supply has been switched off and that it cannot
be accidentally switched on.
Before starting work on the system, switch off the
supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
The LC 110 must be connected in accordance with
the rules and standards in force for the application in
question.
Pos.
Description
Terminal
number
R
Reference electrode.
11
1
Electrode for stop of pump.
12
2
Electrode for start of pump.
22
3
Electrode for high-level alarm.
32
T
M
04
23
41
23
08
This setting determines the actual application type
(3 levels (4 electrodes), page 98)
.
At this setting, the start-up is delayed within the range
from 0 to 255 sec. (random) after the electricity supply
has been switched on
when
the liquid level is
sufficiently high.
Automatic test run carried out every 24 hours.
After the electricity has been switched on, the pump will
start immediately
when
the liquid level is sufficiently
high.
No automatic test run.