P06 Group: Output terminals
P06.03
Relay RO1
output
selection
0: Invalid
1: In operation
2: Forward rotation operation
3: Reverse rotation operation
4: Jogging operation
5: The inverter fault
6: Frequency degree test FDT1
7: Frequency degree test FDT2
8: Frequency arrival
9: Zero speed running
10: Upper limit frequency arrival
11: Lower limit frequency arrival
12: Ready for operation
13: Pre-magnetizing
14: Overload pre-warning
15: Underload pre-warning
16: Completion of simple PLC stage
17: Completion of simple PLC cycle
18: Setting count value arrival
19: Defined count value arrival
20: External fault valid
21: Reserved
22: Running time arrival
23: MODBUS communication virtual terminals output
24
–
26: Reserved
27: Weak light
28: Switching to PV power frequency input (threshold-based)
29: Switching to PV power frequency input (S input-based)
30: Switching to power frequency (threshold- or S input-based)
Note: Function 30 is relay output combining the functions 29 and 28. When one of
the two conditions is met, the relay output frequency is high.
30
○
P06.04
Relay RO2
output
selection
5
○
P06.10
Switch-on
delay of RO1
0.000
–
50.000s
10.000s
○
P06.11
Switch-off
delay of RO1
0.000
–
50.000s
10.000s
○
P06.12
Switch-on
delay ofRO2
0.000
–
50.000s
0.000s
○
P06.13
Switch-off
delay of RO2
0.000
–
50.000s
0.000s
○
P07 Group: Human Machine Interface
P07.01
Function
parameter
copy
Used to set the parameter copying mode.
0: No operation
1: Upload function parameters from the pump controller to keypad
2: Download function parameters (including the motor parameters) from the
keypad to pump controller
3: Download function parameters (excluding motor parameters of the P02 group)
from the keypad to pump controller
4: Download function parameters (only motor parameters of the P02 group) from
the keypad to pump controller
Note:
After the parameter is set to 1, 2, 3 or 4, and the operation is executed, the parameter
is automatically restored to 0.
0
○