6.2 Type key
The example shows a controller for electrically driven pumps in
accordance with EN 12845 with a motor output of 15 kW.
7. Technical data
Inputs
The controller has four digital inputs. See table below. The table
also states terminal designations and the status when activated.
The digital inputs are not short-circuit proof.
Outputs
The controller has five digital outputs which are potential-free
changeover contacts. The signals from the digital outputs can be
passed on to a building management system.
Electrical data of signal relay outputs
8. Control panel
The control panel is divided into three areas:
• operating buttons
• status indicator lights
• fault indicator lights.
Fig. 4
Control panel
8.1 Button functions
Example
QST EN / 1 x 15 kW
Type range
Controller for electrically driven pumps
Controller approval
EN: in accordance with EN 12845
Number of connectable electric motors
Performance of connectable electric motor(s)
Control cabinet:
Sheet steel, grey.
Enclosure class:
IP54.
Dimensions w x h x d:
400 x 600 x 250 mm.
Weight:
Up to approx. 80 kg.
Supply voltage:
3 x 400 V, 50 Hz, PE.
Max. current consumption:
See wiring diagram.
Back-up fuse:
Max. 20 A.
Connecting terminals:
L1, N = 2.5 - 6 mm
2
.
EMC noise emission:
According to EN 61000-6-3.
EMC noise immunity:
According to EN 61000-6-2.
Overvoltage category:
III.
Rated short-circuit current: 6 kV.
Degree of contamination:
2.
Ambient temperature:
5 to +40 °C.
Production country:
Italy.
Designation Digital input
Terminal
Upon
activation
DI1
Pressure switch 1
6 + 7
Open
DI2
Pressure switch 2
8 + 9
Open
DI3
Priming tank level switch
(for starting the pump)
10 + 11
Closed
DI4
Additional pressure
switch for "Pump
running" indication
(pressure in the
discharge line)
12 + 13
Closed
Designation Digital output
Terminal
Upon
activation
AR1
Alarm, voltage supply to
controller
31 + 32
Open
AR2
Automatic pump
requirement
33 + 34
Closed
AR3
Pump running
35 + 36
Closed
AR4
Alarm, voltage supply to
motor
37 + 38
Closed
AR5
Failure to start
39 + 40
Closed
Voltage class:
Category 1.
Insulation voltage:
115 V (in relation to earth).
Insulation test voltage:
1.5 kVAC.
Max. supply voltage:
115 VAC.
Max. load:
2 A, 250 V.
Min. load:
100 mA, 12 VDC.
Max. load power:
230 VA/24 W.
TM
0
5
0
744
1
5
11
Button
Description
Manual stop of pump (only possible when the
selector switch is set to "Test").
Manual start of pump (only possible when the
selector switch is set to "Test").
Test of pressure switch 1
Test of pressure switch 2
Indicator light test
Summary of Contents for EPC 300
Page 1: ...GRUNDFOS INSTRUCTIONS Fire Control EN electric 55 kW Installation and operating instructions...
Page 2: ...2...
Page 23: ...BG 23 8 4 8 1 TM05 0744 1511 Test Test 1 2...
Page 24: ...BG 24 8 2 Status 8 3 Alarms AR1 AR2 AR3 1 2 P1 P1 AR1 AR4 DI4 AR5...
Page 26: ...BG 26 11 10 1 I 2 Test 3 4 Start 8 3 15 5 6 25 Nm 1 2 30 Nm 3 8 7 Stop 8 Auto 9...
Page 27: ...BG 27 12 8 2 15 12 1 Auto I Auto Test Stop O I 1 2...
Page 28: ...BG 28 12 2 1 I 2 Test 3 4 Start 15 1 Stop 2 Auto 3...
Page 29: ...BG 29 12 3 1 Test 2 3 P1 4 Stop 5 P2 6 12 2...
Page 30: ...BG 30 13 14 5 Grundfos 5 12 2 1 2 3 4 EN TM05 4262 2112...
Page 32: ...BG 32 16 Grundfos Grundfos 17 18 1 2 Grundfos Grundfos Grundfos...