8.2 Status indications
The operating status of the fire pump set is indicated by means of
three indicator lights under "Status". The following table provides
an overview of status indications. Status indications can be
forwarded to a building management system as potential-free
indications via an output relay.
8.3 Fault indications
Faults are indicated by means of the two indicator lights under
"Alarms". The following table provides an overview of fault
indications. Fault indications can be forwarded to a building
management system as potential-free indications via an output
relay. Fault indications do not have to be recorded. The indicator
lights go out as soon as the fault has disappeared.
Status
Indicator light
Potential-free signal
Status
Text
Mains voltage correct.
On
Power supply
AR1 activated
The pump has received a start request from the
pressure switch or the level switch in the priming tank.
On
Pump on demand
AR2 activated
The pump is running (automatic or manual start).
On
Pump running
AR3 activated
Checking the function of pressure switch 1.
On
Pressure switch test
-
Checking the function of pressure switch 2.
On
Pressure switch test
-
P1
P1
Status
Indicator light
Potential-free
signalling
Status
Text
Phase failure. No power supply.
Off
Power supply
AR1 not activated
Fault in the power supply to the motor.
On
Power failure
AR4 activated
The pump does not start despite start request, which
means the start relay has energised, but the DI4 contact
remains open.
On
Failure to start
AR5 activated
Summary of Contents for EPC 300
Page 1: ...GRUNDFOS INSTRUCTIONS Fire Control EN electric 55 kW Installation and operating instructions...
Page 2: ...2...
Page 23: ...BG 23 8 4 8 1 TM05 0744 1511 Test Test 1 2...
Page 24: ...BG 24 8 2 Status 8 3 Alarms AR1 AR2 AR3 1 2 P1 P1 AR1 AR4 DI4 AR5...
Page 26: ...BG 26 11 10 1 I 2 Test 3 4 Start 8 3 15 5 6 25 Nm 1 2 30 Nm 3 8 7 Stop 8 Auto 9...
Page 27: ...BG 27 12 8 2 15 12 1 Auto I Auto Test Stop O I 1 2...
Page 28: ...BG 28 12 2 1 I 2 Test 3 4 Start 15 1 Stop 2 Auto 3...
Page 29: ...BG 29 12 3 1 Test 2 3 P1 4 Stop 5 P2 6 12 2...
Page 30: ...BG 30 13 14 5 Grundfos 5 12 2 1 2 3 4 EN TM05 4262 2112...
Page 32: ...BG 32 16 Grundfos Grundfos 17 18 1 2 Grundfos Grundfos Grundfos...