We recommend the following accessories.
*
The Unilift CC pump is supplied with a non-return
valve.
3. Installing the product
3.1 General guidelines
The guidelines for correct mechanical installation of
lifting station are according to EN 12056-4.
•
If the lifting station is installed in a basement with
recurrent penetration of groundwater, we
recommend that you install a drainage pump in a
separate pump sump below floor level. In some
countries the drainage pump is mandatory. If
there is only a risk of penetrating groundwater,
we recommend that you install a float switch
outside the lifting station and connect it to a
controller which indicates high-level alarm in
case of flooding.
•
Fix the tank to the floor.
•
We recommend that you connect a diaphragm
pump to the tank to be able to empty the tank
manually.
•
All outlet pipes from the lifting station, diaphragm
pump and drainage pump must have a backflow
loop, i.e. a bend above the local backflow level.
Commonly, the highest point of the bend must be
above street level. See fig.
•
Surface water must not be discharged into the
lifting station inside the building. Collect and
discharge surface water outside the building.
•
Install a non-return valve at the outlet of the lifting
station to prevent backflow.
•
Fit isolating valves at the inlet and outlet of the
lifting station.
•
The volume of the outlet pipe above the non-
return valve up to the backflow loop must be
smaller than the effective tank volume. See pos.
7 in figures
and
•
In general, a lifting station for black wastewater
must be vented above roof level. However, it is
permitted to lead the vent pipe into the main
building ventilation system. Place special two-
way venting valves outside the building.
•
If the wastewater is discharged into a collecting
line, the collecting line must have a filling ratio of
at least h/d = 0.7. The collecting line must be at
least one nominal diameter bigger after the outlet
pipe connection.
•
Use 45 ° bends to avoid deposits in the pipes.
Outlet pipe
Designation
Quantity
Unolift
Duolift
CC/
KP
APB/
SEG
CC/
KP
APB/
SEG
Non-
return
valve
-*
1
-*
2
Double
nipple
-
1
3
5
Isolating
valve
1
1
1
1
Union nut
-
-
2
2
T-piece,
PVC, 90 °
-
-
1
1
Elbow,
PVC, 90 °
-
-
2
2
Pipe,
∅
50, 2 m
-
-
1
1
Thread
tape
1
1
1
1
Summary of Contents for DUOLIFT Series
Page 1: ...UNOLIFT DUOLIFT Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Page 2: ...2...
Page 30: ...BG 30 3 3 20 25 40 100 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 3 5 3 6 3 TM06 5780 0116...
Page 31: ...BG 31 3 7 100 40 6 1 1 3 2 1 7 1 2 3 4 100 40 TM06 5851 0216...
Page 35: ...BG 35 12 Unilift CC KP TM05 9630 3913...
Page 47: ...BG 47 12 ct 1 a 1 2 7 1 b 2 a 1 2 7 1 3 a 7 1 b 13 c 9 10 4 a 6 mm 5 a...
Page 48: ...BG 48 13 1 2 Grundfos...
Page 49: ...BG 49...
Page 80: ...Deutsch DE 80 Abb 12 Unilift CC KP TM05 9630 3913...
Page 143: ...Espa ol ES 143 Fig 12 Unilift CC KP TM05 9630 3913...
Page 205: ...GR 205 3 3 20 25 40 100 3 4 E 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 3 5 3 6 3 TM06 5780 0116...
Page 207: ...GR 207 3 10 PVC 63 mm 75 mm 75 mm 1451 3 11 3 7 1 2 96615831 3 7 TM06 5859 0216...
Page 210: ...GR 210 12 Unilift CC KP TM05 9630 3913...
Page 222: ...GR 222 12 1 a 1 2 7 1 b 2 a 1 2 7 1 3 a 7 1 b 13 c 9 10 4 a 6mm 5 a...
Page 223: ...GR 223 13 1 2 Grundfos...
Page 234: ...Magyar HU 234 12 bra Unilift CC KP TM05 9630 3913...
Page 256: ...Italiano IT 256 Fig 12 Unilift CC KP TM05 9630 3913...
Page 366: ...Portugu s PT 366 Fig 12 Unilift CC KP TM05 9630 3913...
Page 459: ...CN 459 12 13 1 2 1 a 1 2 7 1 b 2 a 1 2 7 1 3 a 7 1 b 13 c 9 10 4 a 6 mm 5 a...
Page 460: ...Appendix 460 Appendix 1 Fig 1 Unolift 270 Duolift 270 TM06 1067 1514...
Page 461: ...Appendix 461 Fig 2 Duolift 540 TM06 1066 1514...