Settings > I/O settings > Analog inputs > Analog inputs
TM078716
Analog inputs
Related information
8.4.1.1 Analog inputs and measured value
The input value for the selected analog input is set in this display.
Path:
Settings > I/O settings > Analog inputs > Analog inputs >
Analog inputs and measured value
TM078717
Analog inputs and measured value
8.4.2 Digital inputs
The digital input to be set is selected in this display.
As standard, there are 12 digital inputs. The display shows each
input so that its physical location can be quickly identified.
Example
The DI2 digital input on IO 351B (designated terminal 12) is linked
to the function "Contactor feedback, pump 1", and the contactor
type is normally open.
DI1 (CU 362) [10] and DI2 (IO351B-41) [12].
Input
Control unit/
module
Terminal
DI1
CU 362
10
DI2
IO 351B
12
Path:
Settings > I/O settings > Digital inputs
TM078718
Digital inputs
8.4.2.1 Digital inputs and functions
The signal input logic and the digital input function are set in this
display. Four of these functions can be renamed. The default names
are "Extra fault 1" to 4. The default name can be changed by the
user. The new name is shown in the alarm log if an alarm becomes
active.
See section about system alarms.
Path:
Settings > I/O settings > Digital inputs > Digital inputs and
functions
TM078719
Digital inputs and functions
Related information
8.4.3 Analog outputs
The analog output to be set is selected in this display.
As standard, there are three analog outputs. The display shows
each output so that its physical location can be quickly identified.
Example
The AO1 analog output on IO 351B (designated terminal 18) is
linked to the function "VFD frequency, pump 1".
AO1 (IO351B-41) [18].
Input
Module
Terminal
AO1
IO 351B
18
Path:
Settings > I/O settings > Analog outputs