13.1 Adaptation of pit graphics to installation values
• Pump object graphics (the shown register addresses are for
pump 1):
– Presence (pump object drawn or not)
Pump#Status.Presence (register 00401, bit 0)
– Disabled (cross marking) Pump#Status.
Disabled (register 00401, bit 11)
– Pumping mode (Running = green, Stopped = grey)
Pump#Status.Running (register 00401, bit 1).
• Pump top colour (the shown register addresses are for pump
1):
– Red if an alarm is present in Pump#Status.Alarm (register
00401, bit 4) or a monitoring fault (fault in auxiliary device)
in Pump#Status.MonitoringFault (register 00401, bit 2)
– Yellow if a warning is present in Pump#Status.Warning
(register 00401, bit 3)
– Grey if everything is OK for the pump in question.
• Pump control source (the shown register addresses are for
pump 1): Pump#ControlSource (register 00402 [enum]). Letter
marking of pump icon:
– Auto = no marking
– Switch = "S"
– Display = "D"
– Remote = "R".
• Number of float switches: NumberOfFloatSwitches (register
00217).
• Function of float switches 1 to 5:
– FloatSwitch1Function (register 00219 [enum])
– FloatSwitch2Function (register 00220 [enum])
– FloatSwitch3Function (register 00221 [enum])
– FloatSwitch4Function (register 00222 [enum])
– FloatSwitch5Function (register 00223 [enum]).
• Displayed switch position:
– Switch on (1) = up
– Switch off (0) = down.
• Value of float switches 1 to 5: FloatSwitchesStatus (register
00218).
• Type of level and flow measurements: PitSensors (register
00224 [enum]).
• Water level: PitWaterLevel (register 00301 [0.01 m]) shown as
a level sensor value and as a drawing of the water surface. If a
level sensor is not present, the level can be expressed relative
to the position of the installed float switches:
PitSwitchWaterLevel (register 00302 [enum]).
• Flow value:
– PitFlowOut (register 00306 [0.1 l/s]) or
– PitAverageFlowOut (register 00307 [0.1 l/s]).
13.2 Main status
13.2.1 Pit operation display
• Operating mode: OperatingMode (register 00203 [enum]).
• The "Interlock" button will issue the PitControl.InterlockPit
(register 00101, bit 3) command, which brings the pit into
operating mode "Interlocked", and the "Auto" button will issue
the PitControl.AutoPit (register 00101, bit 4) command, which
brings it back into one of the automation modes.
• The "Alarm Ack" button will issue the PitControl.ResetAlarm
(register 00101, bit 0) command, which will clear any alarm/
warning indication (not logs) which does not represent a
present alarm/warning condition, and will make the system
assume automation control without any auto-
acknowledgement delay.
• The "Custom relay" buttons are "radio buttons". Selecting "On"
will issue the value 1 to data item SetCustomRelay (register
00102), and selecting "Off" will issue the value 0.
• Time (real-time clock in the CU 36X control unit):
– Reading and displaying the time is done by using
RealTimeClockHI/LO (register 00228/00229 [unix time]) or
RtcSecond (register 00230), RtcMinute (register 00231),
RtcHour (register 00232), RtcDay (register 00233),
RtcMonth (register 00234), RtcYear (register 00235) if this
time format is preferred.
– The "Set time…" button opens a dialogue that can write the
data item SetRealTimeClockHI/LO (register 00112/00113
[unix time]).
Note
Before trying to operate the CU 361 control unit,
remember to write the ScadaPinCode (register
00109) if PIN code protection has been enabled.